36 Interrupt Function and Pulse Catch Function
36.7 Pulse Catch Function [M8170 to M8177]
31
FN
C
275
-F
N
C
27
9
Da
ta
 
Trans
fe
r 3
32
FN
C
280-
FN
C
289
H
igh Speed 
Pr
ocessing 2
33
FN
C
290-
FN
C
299
E
xtension Fi
le 
R
egister
34
FN
C
300-
FN
C
30
5
FX
3U
-C
F-A
D
P
35
SFC•
STL
Pr
ogr
am
m
ing
36
In
ter
rupt
 
Funct
ion
37
S
pecial
 D
evice
38
Er
ro
r C
ode
A
Ve
rs
ion U
In
fo
rm
atio
n
B
Executi
on
 T
im
es
36.7
Pulse Catch Function [M8170 to M8177]
When the input relay X000 to X007 turns ON from OFF after the FNC 04 (EI) instruction is executed, the special
auxiliary relay M8170 to M8177 is set for interrupt processing.
The FNC04 (EI) instruction is not required in FX
3G
 PLCs.
1. Assignment of input numbers and special auxiliary relays
*1.
Cleared when the PLC mode is changed from STOP to RUN.
*2.
This function is supported only in FX
3U
/FX
3UC
 PLCs.
2. Program example
*1.
When using the pulse catch function at 5 
µs or when receiving a pulse whose response frequency is 50 k to
100 kHz using a high speed counter, perform the following:
- Make sure that the wiring length is 5 m or less.
- Connect a bleeder resistor of 1.5 k
Ω (1 W or more) to the input terminal, and make sure that the load current 
of the open collector transistor output in the counterpart equipment is 20 mA or more including the input 
current in the main unit.
3. Cautions on use
1) When receiving an input again, it is necessary to reset the device which was once set using a program.
Accordingly, until a device is reset, a new input cannot be received.
2) When it is necessary to receive continuous short pulses (input signals), use the external input interrupt function or
high speed counter function.
3) A filter adjustment program is not required.
4) The pulse catch function is executed regardless of the operations of the special auxiliary relays M8050 to M8055
for respectively disabling interrupts.
Pulse catch input
Pulse catch relay
X000
M8170
*1
X001
M8171
*1
X002
M8172
*1
X003
M8173
*1
X004
M8174
*1
X005
M8175
*1
X006
M8176
*1*2
X007
M8177
*1*2
M8170
X002
Reset input
RST
M8170
Y000
When the rising edge of X000 is detected,
M8170 is set as interrupt.
The pulse catch result is reset.
FNC 04
EI
Step
0
The FNC04 (EI) instruction is not required in FX
3G
 PLCs.
Input pulse width
(shown below)
EI
X000(Input)
M8170
X002(Reset)
[X000 to X005]: 5 
µs or more
*1
[X006 and X007]: 50 
µs or more
[X002 and X005]: 50 
µs or more
FX
3U
/FX
3UC
 PLC
[X000, X001, X003 and X004]: 10 
µs or more
FX
3G
 PLC