 Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
38 Error Check Method and Error Code List
38.1 States and Colors of LEDs PLC Operation Status
38.1.6 L RUN LED [FX
3UC
-32MT-LT(-2)]
*1.
FX
3UC
-32MT-LT only.
38.1.7 L ERR LED [FX
3UC
-32MT-LT(-2)]
*1.
FX
3UC
-32MT-LT only.
→ For details, refer to the Hardware Edition of the PLC main unit.
Mode
LED status
PLC status
Action
ONLINE
Lit
Data link is executing
Unlit
Data link is stopped
Take action according to the L ERR LED status.
CONFIG
*1
Lit
Data link is executing
Unlit
Data link is stopped
Take action according to the L ERR LED status.
TEST
Lit
The self-loopback test is
normally finished.
Unlit
The self-loopback test is
abnormally finished.
(This LED is off
while the self-loopback test
is executing.)
Make sure that the power is correctly supplied to the PLC.
If the L RUN LED is not off even after the above check, consult a
Mitsubishi Electric Distributor.
Mode
LED status
PLC status
Action
ONLINE
Lit
Unit disconnected
Outside-control-range station 
error
RD station number setting
error
Securely connect the built-in master to remote I/O units and 
remote device stations on the network.
Make sure that the connected remote I/O units and remote device 
stations are consistent with the detailed information on remote 
stations.
Flickering
All stations are abnormal
Securely connect the built-in master to remote I/O units and 
remote device stations on the network.
Make sure that the connected remote I/O units and remote device 
stations are consistent with the detailed information on remote 
stations.
Unlit
Data link is being normally 
executed
CONFIG
*1
Lit
Used station numbers mismatch. 
(Remote stations are checked 
while the remote station 
information is edited.)
Securely connect the built-in master to remote I/O units and 
remote device stations on the network.
Make sure that the connected remote I/O units and remote device 
stations are consistent with the detailed information on remote 
stations.
Check whether remote device station numbers are within the 
allowable range.
Flickering
All stations are abnormal. 
(Remote stations are checked 
while the remote station 
information is edited.)
Unlit
Data link is being normally 
executed
TEST
Lit
The self-loopback test is 
abnormally finished.
Make sure that the power is correctly supplied to the PLC.
If the L RUN LED is on even after the above check, consult a 
Mitsubishi Electric Distributor.
Unlit
The self-loopback test is normally 
finished.
(This LED is off while the self-
loopback test is executing.)