38 Error Check Method and Error Code List
38.4 Error Code List and Action
31
FN
C
275
-F
N
C
27
9
Da
ta
 
Trans
fe
r 3
32
FN
C
280-
FN
C
289
H
igh Speed 
Pr
ocessing 2
33
FN
C
290-
FN
C
299
E
xtension Fi
le 
R
egister
34
FN
C
300-
FN
C
30
5
FX
3U
-C
F-A
D
P
35
SFC•
STL
Pr
ogr
am
m
ing
36
In
ter
rupt
 
Funct
ion
37
S
pecial
 D
evice
38
Er
ro
r C
ode
A
Ve
rs
ion U
In
fo
rm
atio
n
B
Executi
on
 T
im
es
38.4
Error Code List and Action
When a program error occurs in the PLC, the error code is stored in special data registers D8060 - D8067 and D8438,
D8449. The following actions should be followed for diagnostic errors.
Error 
code
PLC operation at 
error occurrence
Contents of error
Action
I/O configuration error [M8060(D8060)]
Ex-
ample: 
1020
Continues
operation
The head number of unconnected I/O device
1st to 3rd digits: Device number
FX
3G
:10 to 177
FX
3U
/FX
3UC
:10 to 337
4th digit: I/O type
(1 = input (X), 0 = output (Y))
Example: When 1020 is stored in D8060
Inputs X020 and later are unconnected.
Unconnected I/O relay numbers are programmed.
The PLC continues its operation. Modify the program, 
check wiring connection, or add the appropriate unit/
block. 
Serial communication error 2 [M8438 (D8438)]
0000
No error
3801
Continues
operation
Parity, overrun or framing error
Inverter communication, computer link and 
programming:
Ensure the communication parameters are correctly 
set according to their applications.
N:N network, parallel link, etc.:
Check programs according to applications.
Remote maintenance:
Ensure modem power is ON and check the settings of 
the AT commands.
Wiring:
Check the communication cables for correct wiring.
3802
Communication character error
3803
Communication data sum check error
3804
Communication data format error
3805
Command error
3806
Communication time-out detected
3807
Modem initialization error
3808
N:N network parameter error
3812
Parallel link character error
3813
Parallel link sum error
3814
Parallel link format error
3820
Inverter communication error
PLC hardware error [M8061(D8061)]
0000
No error
6101
Stops
operation
RAM error
6102
Operation circuit error
6103
I/O bus error (M8069 = ON)
Confirm for the correct connection of extension cables.
6104
Powered extension unit 24 V failure (M8069 = ON)
6105
Watchdog timer error
Confirm user program.
The scan time exceeds the value stored in D8000.
6106
I/O table creation error (CPU error)
When turning the power ON to the main unit, a 24V
power failure occurs in a powered extension unit. (The
error occurs if the 24V power is not supplied for 10
seconds or more after main power turns ON.)
When turning main power ON, I/O assignment to CC-
Link/LT (built into the FX
3UC
-32MT-LT(-2) PLC) is
disabled.
6107
System configuration error
Check the number of connected special function units/
blocks. Some special function units/blocks have a
connection number limit.
6112
Changed settings for the built-in CC-Link/LT special 
function block cannot be written to the attached flash 
memory cassette.
Verify that the memory cassette is installed 
correctly.
6113
Changed settings for the built-in CC-Link/LT special 
function block cannot be written to the attached write-
protected flash memory cassette.
Set the protect switch to OFF.
6114
CC-Link/LT settings cannot be written to the built-in CC-
Link/LT special function block.
6115
Stops
operation
A built-in CC-Link/LT special function block EEPROM 
writing time-out error occurred, or the built-in CC-Link/LT 
special function block configuration could not be 
completed normally in self CONFIG mode.
1 0 2 0
1: Input (X), 0: Output (Y)
Device number
Example: When X020 is unconnected
BCD conversion value