Mitsubishi Electronics ETH-1000 ユーザーズマニュアル

ページ / 36
 
 
3-1 
Chapter 3 
Connecting Devices to the Network 
The steps of configuring the IP addresses of the ControlLogix PLC system, the ICC ETH-1000 module, and the 
PLC are documented in this chapter.  
3.1   Changing the IP Address of the ControlLogix System 
The  minimum  configuration  of  a  ControlLogix  system  consists  of  a  ControlLogix  chassis  (e.g.  1756-A7),  a 
power supply (e.g. 1756-PA72), a ControlLogix Controller (e.g. 1756-L61), and an EtherNet/IP module (e.g. 
1756-ENBT).  
The  steps  here  document  the  procedure  to  modify  the  IP  address  of  a  1756-ENBT  module  to  add  the 
ControlLogix  system  on  the  same  network  with  the  Mitsubishi  PLC  and  the  ICC  ETH-1000  module.  It  is 
assumed  that  there  is  already  an  IP  address  assigned  to  the  ENBT  module.  If  configuring  a  brand  new 
ENBT module is necessary, please consult the user manual of the Rockwell ENBT module. 
1.  Power  on  the  Rockwell  system  and  monitor  the  display  scrolling  across  the  front  of  the  ENBT 
module. If the module is working properly, the message “OK Rev x.x.x IP1.IP2.IP3.IP4” should scroll 
across  the  display.  Rev  x.x.x  is  the  revision  number  of  the  module  firmware,  and  IP1.IP2.IP3.IP4 
forms  the  current  IP  address  of  the  module.  For  example,  the  message  is  “OK  Rev  2.3.1 
192.168.1.30” 
2.  Connect  a  configuration  PC  on  the  network.  Change  the  IP  address  of  the  PC  to  be  in  the  same 
subnet as the 1756 ENBT module.  
• 
Note:  it  is  assumed  that  changing  the  IP  address  on  a  PC  is  known  by  the  users  of  this 
manual. If required, please consult Windows OS Help File. 
3.  Open  the  RSLinx  Classic  on  the  configuration  PC  and  select  Communications  ->  RSWho  and 
expand the tree to see the following screen showing the system configuration: 
 
In
tr
o
d
u
c
ti
o
n
 
 
S
y
s
te
m
 O
v
e
rv
ie
w
 
 
D
e
v
ic
e
s
 t
o
 t
h
e
 
N
e
tw
o
rk
 
 
C
o
n
tr
o
lL
o
g
ix
 P
L
C
 
P
ro
je
c
C
o
n
fi
g
u
ra
ti
o
n
 
 
E
T
H
-1
0
0
0
 
C
o
n
fi
g
u
ra
ti
o
n
 
 
U
s
in
g
 E
th
e
rN
e
t/
IP
 
E
x
p
li
c
it
 M
e
s
s
a
g
in
g
 
 
T
e
rm
in
o
lo
g
y