Honeywell Work Light DR4300 ユーザーズマニュアル

ページ / 262
 
 
Configuration, Startup, and Operation 
 
 
of Recorder with Display 
12/03 
DR4300 Circular Chart Recorder Product Manual 
93 
Lower Display 
Prompt 
Upper Display  
Range of Setting  
or Selection 
Parameter  
Definition 
RSTABL  
 
 
NO [factory setting] 
KEY 
 
REM1* 
 
 
 
REM2* 
 
 
 
TOTALIZER RESETABLE
—This parameter is used to specify 
whether and how the totalizer value can be reset. 
NO
—Totalizer value cannot be reset. 
KEY
—Totalizer can be reset from the keypad by setting the 
“RESET” parameter to “YES”. 
REM1
—Totalizer will be reset when remote (external) switch 
(digital input 1) goes to ON (contact closure). This totalizer 
reset is independent of any set up of “REMSW1” in the remote 
switch set up group. 
REM2
—Totalizer will be reset when remote (external) switch 
(digital input 2) goes to ON (contact closure). This totalizer 
reset is independent of any set up of “REMSW2” in the remote 
switch set up group.  
CUTOFF 
0 % to 100 % 
LOW CUTOFF VALUE
—Input % of range below which the 
totalizer stops accumulating. 
*Digital input card must be installed.