Power board: Wiring, Software Setup 
17 
J13: E-Stop, Reset 
 
TB6: Molex (F) 
Molex Mating Connector Part #: 430250-0400 (M)  
Molex Crimper Pin Part #: 43030-0008 
 
For Internal Use: 
DT Part #: 014-430250-400 
DT Part #: 014-43030-008 
 
Pin # 
Symbol 
Description 
Reset  
Connect 1-2 to activate the reset. 
Reset 
E-STOP 
Connect 3-4 to engage the E-Stop 
E-STOP 
 
The Turbo Clipper Drive is equipped with a built-in Emergency Stop circuitry. It utilizes two 
latching type relays to enable/disable the drive’s Mosfet transistors. Additionally, the following 
safety and status features are implemented:  
 
 
The E-Stop status, by default, is conveyed to the Turbo Clipper via User Flag Input #4 
(X:$78018,19).See jumper J39. 
 
 
The General Purpose Outputs (GPO), by default, is independent of the E-Stop status. 
They can be disabled in an emergency stop condition. See jumper J36.   
 
 
The Turbo Clipper Drive has an E-Stop software controllable enable bit (Y:$78402,15,1).   
It is a low true logic meaning =0 to engage E-Stop, =1 to disengage E-Stop, allowing the 
user to trigger an emergency stop condition through software logic. 
 
 
Note 
The built-in Emergency Stop circuitry disables the Mosfet 
transistors but does NOT remove power from the DC bus. If this 
additional level of protection is required, it is recommended to 
add a separate external device to remove the DC Bus input from 
the Turbo Clipper Drive.