NOTE: When a 0-10 volt building management system is installed, the return sensor temperature cannot be monitored through the 
boiler display. 
 
NOTE: Ensure that the polarity of the connections from the external modulating boiler controller to the boiler is correct. Reversed 
polarity could lead to erratic and/or no response from the boiler controller. 
K. OPTIONAL UL353 LOW WATER CUT-OFF INTERFACE KIT 
If an optional UL 353 Low Water Cut-Off (LWCO) Interface Kit is used, the control box of the kit should be mounted to the left side of 
the boiler cabinet near the low water cut-off probe, which is located on the outlet nipple of the boiler. 
 
Follow the complete instructions included in the kit for proper installation. 
 
NOTE: The control system senses system water temperatures entering and exiting the heat exchanger to provide protection against 
low water conditions. Where local codes or jurisdictions do not accept a pressure device for low water protection, the jurisdictions may 
accept these control functions as a means of providing low water protection. 
L. WIRING OF CASCADE SYSTEM COMMUNICATION BUS 
1. A Cascade Bus Termination 
Plug has been installed on the 
customer connection board of 
this boiler. The purpose of this 
plug is to stabilize 
communication between multiple 
boilers and reduce electrical 
“noise”. See Figure 31 for 
Cascade Bus Termination Plug 
installation detail. 
 
2. Use standard CAT3 or CAT5 
computer network patch cables 
to connect the communication 
bus between each of the boilers. 
These cables are readily 
available at any office supply, 
computer, electronic, department 
or discount home supply store in 
varying lengths. If you possess 
the skills you can also construct 
custom length cables. 
 
3. It is recommended to use the 
shortest length cable that will 
reach between the boilers and 
create a neat installation. Do not 
run unprotected cables across 
the floor where they may 
become wet or damaged. Avoid 
running communication cables 
parallel and close to or against 
high voltage (120 volt or greater) wiring. Westinghouse recommends that the maximum length of communication bus cables not exceed 
200 feet. 
 
4. Route the communication cables through one of the knockouts in the cabinet. 
 
5. Connect the boilers in a daisy chain configuration as shown below. It is best to wire the boilers using the shortest wire runs rather 
than trying to wire them in the order that they are addressed. The communication bus jacks on the customer connection panel are 
interchangeable so you can use either one or both in any order to connect the cable. 
 
If you have connected the boilers to each other properly, there will be no open communication connection ports. 
 
 
 
Figure 30 
– LP-387-W