5.6.2  Replacing a Cooling Module 
If one of the cooling modules fails, it must be replaced as soon as possible. The cooling module is 
secured to the PSU module with the six (6) screws from the top. To replace the cooling module, 
follow the steps below: 
 WARNING! 
The fan replacement process should be completed within five (5) minutes. If the 
process takes too long, the accumulated heat can damage the subsystem.  
 
 Step 1. 
To remove the cooling module, remove the PSU module first.  
Please follow the PSU removal process listed in the previous 
discussion.   
 Step 2. 
Use a medium-size Phillips screwdriver to remove the six screws 
from the top of the PSU module.    (See  Figure  5-12: Removing a 
 
 
Figure 5-12: Removing a Cooling Module 
 Step 3. 
Remove the cooling fan assembly by the following steps: 
 
Step 3-1. 
Make sure the PSU handle is in the down position so 
that you can grab the edge of the cooling fan assembly.   
 
Step 3-2.  
Use your thumb and middle fingers to seize the 
cooling assembly, your thumb by the upper edge of the fan guard 
and your middle finger at the hemispheric indent.