default write back to write through. If this message appears, the subsystem should be 
properly shut down to avoid data loss. 
Message 5: “Warning: UPS Battery Low 50%” 
This message appears when the UPS battery power level has dipped below 50% of its 
capacity. The default write policy will be changed from the default write back to 
write through. 
Message 6: “UPS Battery restored to safe level” 
This message appears when the UPS battery power level has been restored to above 
50% of its capacity. The write policy will be changed from write through to write 
back. 
Message 7: “UPS AC Power Restored” 
This message appears when the AC power supply to the UPS has been reconnected. 
If the UPS battery power level is below 50%, the write policy will remain as write 
through. If the battery power level is above 50%, the write policy will change from 
write through to write back. 
 
C.6.3 UPS Message Summary 
Table 
C
-1 below summarizes the UPS messages described above.
 It is 
important that you become familiar with these messages and their meanings 
to help maintain the integrity of the data running through your subsystem. 
Message 
AC Power  
 
Battery 
Power 
Level (BPL) 
Write 
Policy 
Status 
UPS connection is absent 
N/A N/A Write 
back 
UPS connection detected 
N/A N/A Write 
back 
Warning: UPS AC Power-
Loss detected 
Disconnected 
BPL > 50% 
Write through 
Warning: UPS Battery 
Low 50%. Please shut 
down to protect data loss 
Disconnected 
BPL < 50% 
Write through 
Warning: UPS Battery 
Low 50%. 
Connected 
BPL < 50% 
Write through 
UPS AC Power Restored 
Reconnected 
BPL > 50% 
Write back 
UPS AC Power Restored 
Reconnected 
BPL < 50% 
Write through 
UPS Battery restored to 
safe level 
Reconnected 
BPL > 50% 
Write back 
Table C-1: UPS Status Messages