Mitsubishi Electronics QD75D ユーザーズマニュアル

ページ / 768
11 - 33
MELSEC-Q
11   MANUAL CONTROL
11.4.4 Creating a program to enable/disable the manual pulse generator operation
A sequence program must be created to execute a manual pulse generator operation.
Consider the "required control data setting", "start conditions" and "start time chart"
when creating the program.
The following shows an example when a manual pulse generator operation is started
for axis 1.
 Required control data setting
The control data shown below must be set to execute a manual pulse generator
operation. The setting is carried out with the sequence program.
Buffer memory address
Setting item
Setting
value
Setting details
Axis
1
Axis
2
Axis
3
Axis
4
Cd.20
Manual pulse
generator 1 pulse
input magnification
1
Set the manual pulse generator 1 pulse input
magnification.
1522
1523
1622
1623
1722
1723
1822
1823
Cd.21
Manual pulse
generator enable
flag
1 (0)
Set "1: Enable manual pulse generator
operation". (Set "0: Disable manual pulse
generator operation" when finished with the
manual pulse generator operation.)
1524 1624 1724 1824
                   Refer to Section 5.7 "List of control data" for details on the setting details.
 Start conditions
The following conditions must be fulfilled when starting. The required conditions
must also be assembled in the sequence program, and the sequence program
must be configured so the operation will not start if the conditions are not fulfilled.
Device
Signal name
Signal state
Axis
1
Axis
2
Axis
3
Axis
4
PLC READY signal
ON PLC CPU preparation completed
Y0
QD75 READY signal
ON QD75 preparation completed
X0
Synchronization flag 
ON
QD75 buffer memory
The access is possible.
X1
Axis stop signal
OFF Axis stop signal is OFF
Y4
Y5
Y6
Y7
Start complete signal
OFF Start complete signal is OFF
X10 X11 X12 X13
BUSY signal
OFF QD75 is not operating
XC
XD
XE
XF
Error detection signal
OFF There is no error
X8
X9
XA
XB
Interface
signal
M code ON signal
OFF M code ON signal is OFF
X4
X5
X6
X7
Drive unit READY signal
ON Drive unit preparation completed
Stop signal
OFF Stop signal is OFF
Upper limit (FLS)
ON Within limit range
External
signal
Lower limit (RLS)
ON Within limit range
If the PLC CPU is set to the asynchronous mode in the synchronization setting, this must be
inserted in the program for interlocking.  If it is set to the synchronous mode, it must not be
inserted in the program for interlocking because it is turned ON when the PLC CPU executes
calculation.