EMC and leakage currents
3
3.1.4
Harmonic Suppression Guidelines
Harmonic currents flow from the inverter to a power receiving point via a power transformer. The Harmonic
Suppression Guidelines were established to protect other consumers from these outgoing harmonic currents.
The three-phase 200V input specifications 3.7kW or less are previously covered by "Harmonic Suppression Guidelines
for Household Appliances and General-purpose Products" and other models are covered by "Harmonic Suppression
Guidelines for Consumers Who Receive High Voltage or Special High Voltage". However, the general-purpose inverter
has been excluded from the target products covered by "Harmonic Suppression Guidelines for Household Appliances
and General-purpose Products" in January 2004. Later, this guideline was repealed on 6 September 2004. All
capacities of all models are now target products of "Harmonic Suppression Guidelines for Consumers Who Receive
High Voltage or Special High Voltage" (hereinafter referred to as "Specific Consumer Guidelines").
"Specific Consumer Guidelines"
This guideline sets forth the maximum values of harmonic currents outgoing from a high-voltage or especially high-
voltage consumer who will install, add or renew harmonic generating equipment. If any of the maximum values is
exceeded, this guideline requires that consumer to take certain suppression measures.
(1) Application of the Specific Consumer Guidelines
Table 1 Maximum Values of Outgoing Harmonic Currents per 1kW Contract Power
Received Power 
Voltage
5th
7th
11th
13th
17th
19th
23rd
Over 23rd
6.6kV
3.5
2.5
1.6
1.3
1.0
0.9
0.76
0.70
22kV
1.8
1.3
0.82
0.69
0.53
0.47
0.39
0.36
33kV
1.2
0.86
0.55
0.46
0.35
0.32
0.26
0.24
Table 2 Conversion factors for FR-A700 series
Class
Circuit Type
Conversion Factor (Ki)
3
Three-phase bridge
(Capacitor smoothing)
Without reactor
K31 = 3.4
With reactor (AC side)
K32 = 1.8
With reactor (DC side)
K33 = 1.8
With reactor (AC, DC sides)
K34 = 1.4
5
Self-excitation three-phase bridge When high power factor converter is used
K5 = 0
Table 3 Equivalent Capacity Limits
Received Power Voltage
Reference Capacity
6.6kV
50kVA
22/33kV
300kVA
66kV or more
2000kVA
Table 4 Harmonic content (Values of the fundamental current is 100%)
Reactor
5th
7th
11th
13th
17th
19th
23rd
25th
Not used
65
41
8.5
7.7
4.3
3.1
2.6
1.8
Used (AC side)
38
14.5
7.4
3.4
3.2
1.9
1.7
1.3
Used (DC side)
30
13
8.4
5.0
4.7
3.2
3.0
2.2
Used (AC, DC sides)
28
9.1
7.2
4.1
3.2
2.4
1.6
1.4
Install, add or renew 
equipment 
Calculation of equivalent 
capacity total
Equivalent 
capacity total
Calculation of outgoing 
harmonic current
Not more than 
harmonic current upper
 limit?
Harmonic suppression 
measures unnecessary
Harmonic suppression 
measures necessary
Equal to or less 
than upper limit
More than upper limit
Above reference 
capacity
Equal to or less 
than reference 
capacity