4.2.50 Watt-hour meter clear/actual operation hour meter clear
(Pr. 170, Pr. 171)
Pr. 170 "watt-hour meter clear"
Pr. 171 "actual operation hour meter clear"
You can clear the watt-hour value and actual operation hour monitoring function.
<Setting>
Write "0" in the parameters to clear the watt-hour value and actual operation hour.
4.2.51 Input terminal function selection (Pr. 180 to Pr. 186)
Pr. 180 "RL terminal function selection"
Pr. 181 "RM terminal function selection"
Pr. 182 "RH terminal function selection"
Pr. 183 "RT terminal function selection"
Pr. 184 "AU terminal function selection"
Pr. 185 "JOG terminal function selection"
Pr. 186 "CS terminal function selection"
Use these parameters to select/change the input terminal functions.
Parameter Number
Factory Setting
Setting Range
170
0
0
171
0
0
REMARKS
The watt-hour value is monitored at the Pr. 52 setting of "25", and the actual operation hour at the Pr. 52
setting of "23".
setting of "23".
Pr. 173 to Pr. 176
Refer to Pr. 160.
Parameter
Number
Terminal
Symbol
Factory Setting
Factory-Set Terminal Function
Setting Range
180
RL
0
Low-speed operation command (RL)
0 to 99, 9999
181
RM
1
Middle-speed operation command (RM)
0 to 99, 9999
182
RH
2
High-speed operation command (RH)
0 to 99, 9999
183
RT
3
Second function selection (RT)
0 to 99, 9999
184
AU
4
Current input selection (AU)
0 to 99, 9999
185
JOG
5
Jog operation selection (JOG)
0 to 99, 9999
186
CS
6
Automatic restart after instantaneous
power failure selection (CS)
power failure selection (CS)
0 to 99, 9999
R elated param eters
P r. 52 "D U /P U m ain display data
selection"