4.2.62 Stop-on-contact control function (Pr. 275, Pr. 276)
Pr. 275 "stop-on-contact excitation current
low-speed multiplying factor"
Pr. 276 "stop-on-contact PWM carrier
frequency"
z
Set "1 or 3" (stop-on-contact control) in Pr. 270. Also advanced magnetic flux vector control must be
selected.
<Wiring and operation examples>
• Sink logic
When both the RT and RL terminals are switched on, the inverter enters the stop-on-contact mode, in which
operation is performed at the frequency set in Pr. 6 "multi-speed setting (low speed)" independently of the
preceding speed.
Parameter 
Number
Factory
Setting
Setting Range
270
0
0, 1, 2, 3, 
275
9999
0 to 1000%, 9999
276
9999
0 to 15, 9999
Note:  The input signal terminals used depend on the Pr. 180 to Pr. 186 settings.
R elated param eters
Pr. 4 "multi-seed setting (high speed)"
Pr. 5 "multi-seed setting (middle speed)"
Pr. 6 "multi-seed setting (low speed)"
Pr. 48 "second stall prevention
Pr. 72 "PWM carrier frequency" 
operation current"
Pr. 180 to Pr. 186 
(input terminal  function selection)
Pr. 270 "stop-on-contact, load torque
high-speed frequency selection"
Lift
<Without stop-on-contact control>
<With stop-on-contact control>
Vibration
Complete stop
Lift
NFB
STF
RH
RM
RL
RT
SD
U
V
W
MC
Motor
Power supply
Stop-on-contact selection 2
Start signal
Multi-speed selection 1
Multi-speed selection 2
Stop-on-contact selection 1
Mechanical
brake
R
S
T
(a)
(b)
(c)
Time
Pr.4
RH
ON
OFF
RM
ON
OFF
RL
ON
OFF
RT
ON
OFF
Pr.5
Pr.6
Output 
frequency
0
Ordinary mode Stop-on-contact control
Goes into stop-on-contact control mode when both 
RL and RT switch on.
Note: (RL and RT may be switched on in any order with
         any time difference.)
         (a) Acceleration time (Pr. 7)
         (b) Deceleration time (Pr. 8)
         (c) Second deceleration time (Pr. 44)