Base frequency, base frequency voltage (Pr. 3, Pr. 19, Pr. 47, Pr. 113)
Pr. 3 "base frequency"
Pr. 19 "base frequency voltage"
Pr. 47 "second V/F (base frequency)
Pr. 113 "third V/F (base frequency)
Used to adjust the inverter outputs (voltage, frequency) to the motor rating.
z
 When running a standard motor, generally set the rated motor frequency. When running the motor using
the commercial power supply-inverter switch-over, set the base frequency to the same value as the power
supply frequency.
z
 Always set this frequency to "50Hz" if the frequency indicated in the motor rating plate is "50Hz" only. If the
setting remains unchanged from "60Hz", the voltage may become too low and torque less, resulting an
overload trip. Especially, care must be taken when Pr. 14 "load pattern selection" = 1.
<Setting>
• Use Pr. 3, Pr. 47 and Pr. 113 to set the base frequency (rated motor frequency). Three different base
frequencies can be set and the required frequency can be selected from among them.
• Pr. 47 "second V/F (base frequency)" is made valid when the RT signal turns on, and Pr. 113 "third V/F
(base frequency)" is made valid when the X9 signal turns on. Use any of Pr. 180 to Pr. 186 to assign the
terminal used for X9 signal input. (Note 4)
• Use Pr. 19 to set the base voltage (e.g. rated motor voltage).
Parameter 
Number
Factory Setting
Setting Range
Remarks
3
60Hz
0 to 400Hz
19
9999
0 to 1000V, 
8888, 9999
8888: 95% of power 
supply voltage
9999: Same as power 
supply voltage
47
9999
0 to 400Hz, 9999
9999: Function invalid
113
9999
0 to 400Hz, 9999
9999: Function invalid
Note: 1. When using the Mitsubishi constant-torque motor, set Pr. 3 "base frequency" to 60Hz.
2. When the advanced magnetic flux vector control mode has been selected using Pr. 80 and 
Pr. 81, Pr. 3, Pr. 47, Pr. 113 and Pr. 19 are made invalid and Pr. 84 and Pr. 83 are made valid.
However, Pr. 3, Pr. 47 or Pr. 113 is made valid for the S-shaped inflection pattern point of Pr. 29.
3. When "2" (5-point flexible V/F characteristics) is set in Pr. 71, the Pr. 47 and Pr. 113 settings are
made invalid.
Also, "8888" and "9999" can not be set in Pr. 19.
4. The RT (X9) signal acts the second (third) function select signal and the other second (third)
functions are also made valid. Refer to page 159 for Pr. 180 to Pr. 186 (input terminal function
selection).
Related parameters
Pr. 14 "load pattern selection"
Pr. 71 "applied motor"
Pr. 80 "motor capacity"
Pr. 81 "number of motor poles"
Pr. 83 "rated motor voltage"
Pr. 84 "rated motor frequency"
Pr. 180 to Pr. 186 (input terminal 
                function selection)
Pr.19
 Pr.3
 Pr.47
 Pr.113
Output frequency (Hz)
Ou
tpu
t volta
g
e