Honeywell DR4300 ユーザーズマニュアル
Troubleshooting and Pen Alignment
of Recorder without Display
12/03
DR4300 Circular Chart Recorder Product Manual
167
7.3.4 Chart Rotation Troubleshooting
Procedure
Table 7-4 explains how to troubleshoot a chart rotation problem.
Table 7-4 Troubleshooting Chart Rotation Failure Symptoms
Step
What to do
How to do it or
where to find the instructions
1
Check the chart installation.
Turn the chart until the desired time line on the
chart is aligned with the time index on the chart
plate and pen 1 before closing the locking clip on
the hub. Push down on the lifter to return the
pen(s) to the chart.
chart is aligned with the time index on the chart
plate and pen 1 before closing the locking clip on
the hub. Push down on the lifter to return the
pen(s) to the chart.
CAUTION: Do not try to rotate the hub
2
Check the settings of the configuration
switches. Change settings if incorrect for
application.
switches. Change settings if incorrect for
application.
Refer to Section 3 – Configuration, Startup, and
Operation of Recorder without Display.
Operation of Recorder without Display.
3
Run the step test.
Refer to Section 3 – Configuration, Startup, and
Operation of Recorder without Display
(Subsection 3.3.3).
Operation of Recorder without Display
(Subsection 3.3.3).
4
Check the motor cable plug connection at
connector P3 on the printed circuit
assembly for pen 1.
connector P3 on the printed circuit
assembly for pen 1.
Power down the recorder, then visually examine
the plug and reseat it.
the plug and reseat it.
5
Replace the chart motor.
Refer to the replacement procedure in Section 9
– Replacing Hardware Assemblies.
– Replacing Hardware Assemblies.
6
Replace the printed circuit board for pen
1.
1.
Refer to the replacement procedure in Section 9
– Replacing Hardware Assemblies.
– Replacing Hardware Assemblies.