DR4300 Circular Chart Recorder Product Manual
12/03
D.2 Starting and Stopping Tuning with Accutune II
Procedure
After “TUNE” has been enabled in the tuning set up group as described in Section 4, use the procedure in
Table D-1 to start tuning.
Table D-1 to start tuning.
To abort tuning in progress, press the MAN/AUTO/RESET key to take the recorder out of Auto mode.
The message “AbRT” (abort) will be displayed as the value of tuning set up group parameter “AT ERR”.
The tuning parameters will retain the values they had at the start of the Accutune operation.
The message “AbRT” (abort) will be displayed as the value of tuning set up group parameter “AT ERR”.
The tuning parameters will retain the values they had at the start of the Accutune operation.
Table D-1 Procedure for Starting Accutune II
Step Press
Action/Result
1
DISP
until you see
Lower Display
TuneOF
If “TuneOF” (tune off) does not appear, then
Accutune is not enabled.
Accutune is not enabled.
2
or
to toggle to
Lower Display
TuneON
Tuning will begin and the lower display will flash
“TUNING”. When tuning has been completed the
lower display will again show “TuneOF”.
lower display will again show “TuneOF”.