3.4 I/O Signal for Programmable Controller CPU
3.4.1 List of I/O signal
3
SPECIFICATIONS
3.4
I/O Signal for Programmable Controller CPU
3.4.1
List of I/O signal
The following shows the list of I/O signal of a local module to the programmable controller 
CPU.
The I/O signal is assigned, assuming that start I/O number of a local module is "0000".
Replace it with the I/O signal of a slot where the local module is mounted.
Note that a local module cannot be mounted to the main base unit.
The device X is an input signal from a local module to the programmable controller CPU, 
and the device Y is an output signal from the programmable controller to a local module.
Table 3.9 List of I/O signal
Signal direction
Local module
Programmable controller CPU
Signal direction
Programmable controller CPU
Local module
Device 
No.
Signal name
Device 
No.
Signal name
X0
Link status
OFF: Online
ON: Offline, station-to-station test, or self-loopback test
Y0
Use prohibited
X1
B/W initial value setting status
OFF: B/W initial value setting completed
ON: B/W initial value setting in execution
Y1
X2
Use prohibited
Y2
X3
Y3
X4
Y4
X5
Y5
X6
Y6
X7
Refresh ready status
OFF: refresh not requested
ON: Refresh requested
Y7
X8
Use prohibited
Y8
X9
Y9
XA
YA
XB
YB
XC
YC
XD
YD
XE
YE
XF
YF