Motorola 3460 ユーザーズマニュアル

ページ / 188
3460 Fast’R
1-12
Fan and Deflector Requirements
Forced-air cooling for up to four rack-mounted enclosures can be 
provided by fans and a deflector, mounted below the enclosures, to 
provide passive, bottom-entry rear exhaust and upward-forced, front-
entry cooling air. Refer to Figure 1-6. The airflow requirement is 80 
CFM (2266230 CCM). 
For example, three fans rated 117 CFM (202176 CCM) at a static 
pressure of 0 inches of water provide enough airflow, when cooling four 
enclosures. The deflector ensures that hot air from equipment below the 
enclosures does not mix with enclosure-cooling air. The cabinet must 
have venting at the top or rear to let exhaust air escape.
Figure 1-6. Cabinet Arrangement
Three or More Enclosures
Unit 2
Fan Chassis 2
Unit 1
Fan Chassis 1
AccessWay 
AccessWay 
AccessWay 
AccessWay