Hearth & Home Technologies QVI-25FB-S ユーザーズマニュアル

ページ / 40
Quadra-Fire  •  QVI-25FB-S  •  2031-910 Rev. E  •  9/08
8
Fire Risk.
Asphyxiation Risk.
•  Terminations MUST meet minimum clearances.
•  Exhaust gases are hot.
•  Nearby vents may draw fumes into house.
A.  Vent Termination Minimum Clearances
Figure 4.1 specifi es minimum vent heights for various 
pitched roofs.
Roof Pitch 
H (Min.) Ft.
Flat to 6/12...........................................................1.0*
Over 6/12 to 7/12 .................................................1.25*
Over 7/12 to 8/12 .................................................1.5*
Over 8/12 to 9/12 .................................................2.0*
Over 9/12 to 10/12 ...............................................2.5*
Over 10/12 to 11/12 .............................................3.25
Over 11/12 to 12/12 .............................................4.0
Over 12/12 to 14/12 .............................................5.0
Over 14/12 to 16/12 .............................................6.0
Over 16/12 to 18/12 .............................................7.0
Over 18/12 to 20/12 .............................................7.5
Over 20/12 to 21/12 .............................................8.0
Figure 4.1  Minimum height from roof to lowest discharge  
 opening
Termination Locations 
 
* 3 foot minimum in snow regions
WARNING
HORIZONTAL 
OVERHANG
VERTICAL 
WALL 
GAS DIRECT VENT 
TERMINATION CAP
12
X
ROOF PITCH 
IS  X/ 12 
LOWEST
DISCHARGE
OPENING
2 FT. 
MIN.
20 INCHES MIN.
H (MIN.) - MINIMUM HEIGHT FROM ROOF 
TO LOWEST DISCHARGE OPENING