Eclipse Combustion 5600 ユーザーズマニュアル

ページ / 42
34
Eclipse Veri-Flame Instruction Manual 818 -2/02
Table 9.1
  Veri-Flame Operating Sequence
POWER ON
Was internal safe start check successful?
EXTERNAL INTERLOCK CHECKS
Is flame signal present?
BURNER START-UP
(see next page)
YES
NO
YES
NO
YES
NO
YES
NO
Various lockout messages
Fan output is energized; modu-
lator is sent to low fire.
YES
NO
Holds until answer is yes.
Is main valve closed switch made?*
* Applies to purge and no purge models only.
Is voltage present at air flow switch?
Is voltage present at interlock switch?
ERROR MESSAGE
MAIN VALVE  FAIL
XX:XX:XX  LOCKOUT
ERROR MESSAGE
LIMITS OPEN
TIME = XXXX:XX:XX
NORMAL MESSAGE
FAN ENERGIZED
ERROR MESSAGE #1
UNSAFE FLAME ON
NORMAL MESSAGE
REMOTE DISPLAY
REVISION X.X
Alarm energized.
Fan is energized. If signal is elimi-
nated within 30 seconds, se-
quence continues. If not, then . . 
ERROR MESSAGE #2 – 30 SECONDS AFTER #1
UNSAFE FLAME ON
XX:XX:XX  LOCKOUT
ERROR MESSAGE #1
UNSAFE AIR SHORT 
Alarm energized.
If switch is opened within 30 
seconds, sequence continues. If 
not, then . . .
ERROR MESSAGE #2 – 30 SECONDS AFTER #1
UNSAFE AIR SHORT
XX:XX:XX  LOCKOUT
FOR PURGE & MODULATING
NORMAL MESSAGE
SAFE START OK
Check_Sum = XX