Honeywell 62-2030-01 ユーザーズマニュアル

ページ / 28
STRYKER VAV USER GUIDE
62-2030—01
22
14. FLOW BALANCING
The flow balancing view is used to balance a controller that is 
programmed with a standard VAV application. Based on the 
version of the VAV application and its features, the following 
operations can be performed on the view.
• Flow pressure zero calibration
• Two point calibration
• K factor calibration
• Heating coil water flow calibration.
• Pre-requisites
• The controller must be online.
• The controller must be in a commissioned state.
• VAV Zone Terminal Single Duct must be selected as the 
Application Type and Air Balance Supported must be 
selected.
NOTE: Note: The selections must be done before down-
loading the program to the controller.
• Select the Reheat Valve Override Supported option to 
calibrate the reheat valve.
• Select the Peripheral Heat Valve Override Supported 
option to calibrate the peripheral heat valve.
To flow balance:
14.1 Fields
Table 13. Flow Balancing Fields.
Flow pressure zero calibration
To start zero balancing:
Click 
Start Zero Balancing.
The damper is completely closed. If any flow pressure is 
detected, that value is considered to be the flow pressure 
offset. After the completion of zero balancing, the device 
mode is set to automatic operation.
Step
Action
1
On the 
Nav palette, browse to Station > Config > DriversLonNetwork > LonDevice.
or 
Browse to 
Station > Config > DriversBacnetNetwork > BacnetDevice.
2
Right-click ControlProgram and select 
Views > Flow Balancing View. The Flow Balancing View appears on 
the right pane.
You can type the values into the following fields.
Name
Description
Actuator Travel Time The actuator travel time is the time required by the actuator to travel from 0% to 100% open or 100% to 
0% open. This time interval depends on the actuator type and can vary from 0 to 500 seconds.
K Factor
This field allows you to manually change the K factor value from 0 to 10000.
Inlet Area
Displays the area of the duct. Either a standard diameter can be selected or a custom area can be 
entered in this field. The inlet area ranges from 0 to 100 sq.ft.
Measured Flow
Displays the actual air flow when measured by the balancer using an accurate device. This field is 
editable.
Maximum Flow 
Setpoint
This field allows you to set the flow setpoint from 0 to 138850 cfm for maximum flow calibration and k 
factor calibration. The controller seeks stable flow and when it is reached, it allows you to set the 
calibration source value.
Minimum Flow 
Setpoint
This field allows you to set the flow setpoint value from 0 to 138850 cfm. You must set the flow setpoint 
less than the maximum value to obtain minimum flow calibration. The controller seeks stable flow and 
when it is reached, it allows you to set the calibration source value.
Re-heat Valve 
Override
This field allows to override the value of the reheat valve in an application built for the reheat valve. This 
field is visible when the 
Reheat Valve Override Supported feature is selected in the Details View of 
the 
Control Program.
Peripheral Heat 
Valve Override
This field allows to override the value of the peripheral heat valve in an application built for the 
peripheral heat valve. This field is visible when the 
Peripheral Heat Valve Override Supported feature 
is selected in the 
Details View of the Control Program.
Device Mode
Displays the current device mode. This is a non-editable field.
Damper Position
Displays the current damper position. This is a non-editable field.
Sensed Flow
Displays the actual air flow that is measured by a pressure sensor. This field is non-editable.
Flow Pressure
Displays the current flow pressure. This field is non-editable.