Configuring via the Web Server
Configuring the System
Steps
: Use the descriptions in the table below to configure the Status, Egress, and Tamper inputs, then 
click 
Submit Changes
:
Table 2-7:  Configuration > Doors > Inputs Tab Field Descriptions
Setting
Description
Mode
Normally Closed
 – Specifies that the door’s normal state is 
closed.
Normally Open
 – Specifies that the door’s normal state is open.
Unsupervised
 – Specifies that the door’s electrical circuit is 
wired in one path without alternative paths supervised by 
resistors.
Supervised 
– Specifies that the door’s electrical circuit is wired 
with alternative paths supervised by resistors.
R1 & R2 Values
 – Specifies the resistor values being used in the 
supervised modes. The default is 2.2K.
Shunt Time
Specifies the amount of time for which the inputs will be 
shunted, or de-activated. For example, it specifies how long a 
door strike will remain released. Enter the desired number of 
hours (1024 maximum), minutes (60 maximum), and seconds 
(60 maximum). The sum of all three units comprises the shunt 
time. Note that you can express seconds in tenths of a second.
Time Zones
Shunt
 – Specifies the time period during which the input will be 
ignored.
Disable Interlock
 – Specifies the time period during which the 
programmed action on this input from another point will be 
disabled.
Disable Alarm Msgs
 – Specifies the time period during which 
Alarm and Normal will not be reported, but Short and Cut will 
be reported.
Auto-Relock
Causes the door to re-lock immediately when the door status 
switch closes after entry. The output relay that controls the door 
strike de-energizes when the associated input returns to normal 
state instead of remaining energized for the duration of the pulse 
time. To enable Auto-Relock, de-select the 
Disable
 checkbox, 
and select the associated output from the drop down list.