Programming Function Blocks and Features  
 
Video Recorder – User Manual 
 
117
 Logic 
The input or inputs are processed by a logic operator.  Call the result of this logic operation “Result”.  
Result is a pulse that goes ON(1) when the logic is true, and OFF(0) when the logic is not true.  Result 
is then processed according to the specified condition type and condition time.  The final output is a 
discrete pulse CVn OS.  See Figure 4-5. 
LOGIC
OPERATOR
Inputs
A
B
C
D
E
F
G
H
Result
CONDITION
TYPE
&
CONDITION
 TIME
CVn OS
 
Figure 4-5   Logic Signal Flow 
Table 4-25 describes the Logic prompts. See Table 4-2 for additional prompts. 
 
Table 4-25   Logic Prompts 
 
 
 
Prompt 
Range/Selections 
Definition 
OPERATOR 
AND, OR, XOR, RESET/SET FF, 
TOGGLE/FF, ONE SHOT, PASS 
See Table 4-26. 
INPUT A 
OFF, discrete parameter, 0, 1. 
Program at least 2 inputs.  Only inputs 
programmed with parameter, 1, or 0 are processed 
with the operator. 
INPUT B 
 
 
INPUT C 
 
 
INPUT D 
 
 
INPUT E 
 
 
INPUT F 
 
 
INPUT G 
 
 
INPUT H 
 
 
CONDITION TYPE 
NONE, DELAY, EXTEND, PULSE, 
RT PULSE 
See Table 4-20 on page 111. 
CONDITION TIME 
OFF or number 
Enter number of seconds of condition time.  See 
Table 4-20 on page 111.