Honeywell VRX180 ユーザーズマニュアル

ページ / 294
Setpoint Profiler 
 
Video Recorder – User Manual 
 
194
 
Table 5-5   Edit Profile Prompts (continued) 
Prompt 
Range/Selections 
Definition 
AUTO CYCLE 
OFF, ON 
Select ON to have the profile (or batch phase if 
defined) repeat AUTO CYCLE COUNT times. 
Automatically re-runs the profile when ON.  The 
parameter AUTO CYCLE COUNT controls the 
number of additional cycles through the profile.  
When AUTO CYCLE is ON and AUTO CYCLE 
COUNT is zero (0), the profile will cycle forever. 
For a single phase profile, the profiler must 
progress to the END state before cycling back 
to segment 1.  Once the profiler is ENDed, the 
automatic cycling function will change the 
profiler to the READY state for one machine 
cycle (clearing the profiler’s discrete outputs) 
before proceeding to the RUN state.  The 
elapsed time of the profiler will continue due to 
re-cycling. 
For a multiphase profile, the profiler must 
progress to the END state following segment 
BATCH LAST SEGMENT before cycling back to 
the BATCH FIRST SEGMENT.  Once the 
profiler is ENDed, the automatic cycling 
function will change the profiler to the RUN 
state.  The elapsed time of the profiler will 
continue running during recycling. 
AUTO CYCLE COUNT 
0-254 
0:  the profile (or batch) will repeat forever. 
1-254: the profile (or batch) will repeat this 
many times. 
EDIT PROFILE LOOPS 
LOOP #1-4 
 
FROM SEGMENT # 1-63 
 
TO SEGMENT # 1-63 
 
REPEAT COUNT  1-999 
Define up to 4 loops per profile.  Note that the 
repeat count is the number of loop repetitions, 
not the number of loop executions.  See Loop 
Segments
 on page 184 for details. 
JUMP FROM 
SEGMENT 
0-63 
The profile can be forced to jump from any 
segment to any other segment.  A jump within a 
loop will continue that loop.  A jump outside a 
loop will exhaust that loop.  A jump outside the 
batch phase will exhaust any auto cycling in 
effect. 
At the completion of this segment, the profiler 
will jump to the beginning of JUMP TO 
SEGMENT. 
JUMP TO SEGMENT 
0-63 
At the completion of JUMP FROM SEGMENT, 
the profiler will jump to the beginning of this 
segment.