Mitsubishi Electronics QD75MH1 ユーザーズマニュアル

ページ / 838
 
 
 
6 - 52 
MELSEC-Q
 
6   PLC PROGRAM USED FOR POSITIONING CONTROL 
 
6.5 Program details 
6.5.1 Initialization program 
[1]   OPR request OFF program 
This program forcibly turns OFF the "OPR request flag" (
Md.31
Status: b3) 
which is ON. 
When using a system that does not require OPR, assemble the program to 
cancel the "OPR request" made by the QD75MH when the power is turned ON, 
etc. 
 
 Data requiring setting 
 
Set the following data to use the OPR request flag OFF request. 
 
Buffer memory address 
Setting item 
Setting 
value 
Setting details 
Axis 1  Axis 2  Axis 3  Axis 4 
Cd.19
 
OPR request flag OFF 
request 
Set to "1: Turn OPR request flag OFF". 
1521  1621  1721  1821 
 
                   Refer to Section 5.7 "List of control data" for details on the setting details. 
 
 Time chart for OPR OFF request 
 
OFF
ON
OFF
0
1
0
ON
OFF (0)
PLC READY signal
 [Y0]
QD75 READY signal 
[X0]
OPR request OFF flag
[  Md. 31 Status: b3]
Cd. 19 OPR request flag OFF request
 
 
Fig. 6.1 Time chart for OPR OFF request 
 
[2]   External command function valid setting program 
This program is used to validate the "external command signal" beforehand when 
using the external command functions (external start, speed change, speed-
position switching, position-speed switching, skip). (Set which function to use 
beforehand in "
Pr.42
External command function selection".) 
Set the following data to validate the "external command signal". 
 
Buffer memory address 
Setting item 
Setting 
value 
Setting details 
Axis 1  Axis 2  Axis 3  Axis 4 
Cd.8
 
External command valid 
Set to "1: Validate external command". 
1505  1605  1705  1805 
 
 Refer to Section 5.7 "List of control data" for details on the setting details.