Honeywell 301C ユーザーズマニュアル

ページ / 107
Honeywell 301C User Manual 
IAQPoint2 continued
 
 
 
Data Type
Required
1
Storage 
Type
2
BACnet 
Writeable?
Value
object_identifier 
R
C
N
Sensor number * 256 + 1.  Sensor number 
for RH is Modbus address + 2.  For example 
an IAQPoint2 at Modbus address 005 will 
appear as 1793 or 0x0701.
object_type
enumerated
R
C
N
analog_input (0)
event_state
enumerated
R
R
N
if temp sensor fault, fault (1),
else normal (0)
object_name
character string
R
N
N
"IAQPoint RH   AdXXX .RH" where XXX  is 
the Modbus address plus two.
out_of_service
boolean
R
R
N
FALSE
present_value
real
R
R
N
Relative Humidity in percent
reliability
enumerated
O
R
N
As appropriate reports
no_fault_detected (0) or
no_sensor (1) or
unreliable other (7)
Fault is detected within 60 seconds
status_flags
in_alarm
boolean
R
R
N
if not purchased or faulty "true" (1)
else "false" (0)
fault
boolean
R
R
N
if not purchased or faulty "true" (1)
else "false" (0)
overridden
boolean
R
C
N
False (0)
out_of_service boolean
R
R
N
False (0)
units
enumerated
R
N
N
percent_relative_humidity (29)
Notes
1  --  'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --  'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
continued…
Group
Property
IA
Q
Po
in
t RH
An
al
og
 In
pu
ts
78