ユーザーズマニュアル目次Once per second1Low1155 - 2801The Back-UPS will switch to battery power less often. Use with equipment that is not sensitive to...1Twice per second1Medium (factory default)1160 -2801Default, use in normal conditions.1Three times per second1High1165 - 2701The Back-UPS will switch to battery power during any small fluctuation in voltage. Use with equip...1Connect the Battery and Turn on the Unit1Status Indicators1On1Off1On-line - Back-UPS is supplying conditioned utility power to the connected equipment1On (Off during 4 beeps)14 beeps repeated every 30 seconds1On-Battery - Back-UPS is supplying battery power1Flashing1Rapid Beeping (every 1/2 second)1Low Battery Warning - The Back-UPS has 1.5 minutes of remaining battery power1Flashing1Constant tone1Bad Battery Detected - Battery needs to be charged, or is at end of life. (See Battery Replacement.)1Off1Short beep every 4 seconds1Low Battery Shutdown - During On Battery operation the battery power was almost completely exhaus...1Off1Constant Tone1On Battery Overload - Connected equipment requires more power than provided by the Back-UPS batte...1On1Constant Tone1On Line Overload - The power drawn by the connected equipment exceeds the power capacity of the B...1Flashing1Chirp every 2 seconds1Charger Warning -Back-UPS has experienced an internal problem, but continues to power the load. C...1Off1Constant Tone1Charger Fault - Back-UPS has an internal problem, and is no longer powering the load. Contact APC...1Specifications2Input2Voltage2230 Vac nominal2Frequency245-65 Hz2Brownout Transfer2160 ±8% VAC, typical2Over-voltage Transfer2280 VAC, typical2Output2UPS Capacity (total)2500 VA / 300 W2Voltage On Battery2230 Vac rms2(step-approximated sine wave)2Frequency - On Battery250 Hz ±1 Hz, 60 Hz ±1 Hz2Transfer Time250 Hz: 6ms typical, 10ms maximum 60 Hz: 5ms typical, 8ms maximum2Protection and Filter2AC Surge Protection2Full time, 273 joules2AC Input2Re-settable circuit breaker2Battery2Type2Maintenance free2Average Life22 - 5 years depending on the number of discharge cycles and environmental temperature2Typical Recharge Time210 Hours2Physical2Net Weight25.4 kg2Dimensions (H x W x D)218.55 cm (H) x 11.5 cm (W) x 21.3 cm (D)2Operating Temperature20 oC to 40 oC (32 oF to 104 oF)2Storage Temperature2-15 oC to 45 oC (5 oF to 113 oF)2Operating Relative Humidity20 to 95% non-condensing2Operating Elevation20 to 3000 m (0 to 10,000 ft)2Adjusting Transfer Voltage and Sensitivity Settings11 . Ensure the Back-UPS is off. Plug it into utility power.12 . Press and hold ON/OFF until the LED repeatedly flashes. The unit is now in Program Mode.13 . Release the button. The LED will flash once, twice, or three times per second, indicating the...14 . Press ON/OFF within two seconds to change the setting. Each time the button is pressed, the L...15 . To exit Program Mode, release the button and wait for the LED to stop flashing.1Connect Equipment1Kết nối Thiết bị3Nối Ắc quy vào và Bật Bộ Lưu điện lên3Điều chỉnh Điện áp Chuyển và Các Thiết lập Độ nhạy3Các Chỉ thị Trạng thái3Xử lý trục trặc4Đặc điểm kỹ thuật4Thay Ắc quy4Bảo hành4Bảo dưỡng4连接设备5连接电池并启动装置5调节转换电压和敏感度设置5状态指示灯5故障排除6规格6电池更换6保修服务6服务6連接設備7連接電池並開啟裝置7調整傳輸電壓和敏感度 設定7狀態指示燈7故障排除8規格8電池更換8保固8維修8サイズ: 891KBページ数: 8Language: 中文(zhōngwén)マニュアルを開く