System Maintenance
36
Table 9
Troubleshooting
Symptom
Possible Cause
Check or Remedy
Condenser will not start
No power to condenser
Check voltage at input terminal block
Circuit breaker for low voltage 
transformer in condenser is tripped
Locate problem in condenser electrical 
panel and repair
No low voltage signal to/from indoor unit Locate open circuit and repair
Low indoor unit
suction pressure
Insufficient refrigerant in system
Check for leaks, repair, and add refrigerant
Fan-cycling ambient thermostats
setpoints too low
Check schematic for recommended 
setpoints and adjust.
Low discharge pressure
Faulty head pressure control valve
or condenser FSC/VFD control
Replace if defective
High discharge pressure
Dirty condenser fins
Clean coil
Condenser fans not operating
Check for low voltage signal from indoor unit
Check fan motors and fuses
Check for correct ambient thermostat 
setpoints, as applicable.
High refrigerant charge
Check refrigerant charge
VFD Condenser trips out 
on overvoltage
(OU displayed on VFD 
controller)
Supply voltage is Delta configuration
or is ungrounded/high impedance
Shut off AC voltage, locate the VFD, pull out 
the EMC tab and reconnect power
TVSS indicator lights are 
extinguished or red LED is 
illuminated and monitoring 
terminals 11/12 are closed
No voltage or improper phasing exists
at condenser
Check voltage at input terminal block
Electrical connections to TVSS are 
faulty
Locate connection problem and repair
A surge exceeding the rating
of the TVSS has occurred
Replace TVSS and inspect other 
components for damage and replace them if 
necessary