Roberts Gorden UHA[X][S] 125 사용자 설명서

다운로드
페이지 62
SECTION 6: V
ENTING
19
Figure 12: Separated Combustion Heater - Vertical and Horizontal Vent Termination
Figure 13: Concentric Vent Box
Vent
Termination
Listed Thimble
through
Combustible Wall
4" (10 cm) 
Diameter Vent
12" (31 cm)
Minimum from wall
to vent termination.
4" (10 cm) 
Diameter
Air Intake
12" (31 cm)
Minimum from air inlet to vent
termination (may be horizontal
or vertical clearance).
Air Intake
Termination
4" 
(10 cm) 
Diameter Vent
4" (10 cm) Diameter
Air Intake
12" (31 cm)
Minimum from air inlet to vent
termination (may be horizontal
or vertical clearance).
Vertical
Option
Horizontal
Option
12" (31 cm)
Minimum from wall
to vent termination.
NOTE: Vent supports not
 shown.
Model
Air Intake & Vent Diameter Part Number
 UHA[X]S  30 - 125
4" (10 cm)
90502102
4" (10 cm) Single
Wall Vent Pipe
(By Others)
Seal joint between single wall
and Type B vent with silicone sealant.
Use 3 sheetmetal 
screws equally
spaced around joint.
Use 3 sheetmetal 
screws equally
spaced around collar.
Concentric
Vent Box
6" (15 cm) Single
Wall Inlet Air Pipe
(By Others)
One piece of 4" (1
0 cm) diamet
er, 1/4" (6 cm) air
space t
ype
 “B” v
ent. Selkir
k Model R
V or e
quivalent.
 (By other
s)
Combustion Air 
to Heater
Toward
Outside
Exhaust 
from Heater