York 292443-XTG-D-0508 사용자 설명서

다운로드
페이지 28
292443-XTG-D-0508
Johnson Controls Unitary Products
13
TABLE 8: SIDE SUPPLY AIR BLOWER PERFORMANCE
1
MODEL #
DNA
MTR
SPD
EXTERNAL STAIC PRESSURE - IWG
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
1.10
CFM
 WA
T
T
S
CFM
 WA
T
T
S
CFM
 WA
T
T
S
CFM
 WA
T
T
S
CFM
 WA
T
T
S
CFM
 WA
T
T
S
CFM
 WA
T
T
S
CFM
 WA
T
T
S
CFM
 WA
T
T
S
CFM
 WA
T
T
S
CFM
 WA
T
T
S
030
HI
-
-
-
-
1238
504
1165
484
1075
463
984
443
894
422
751
390
-
-
-
-
-
-
MED
994
333
947
321
901
309
854
297
774
280
-
-
-
-
-
-
-
-
-
-
-
-
LOW
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
036
HI
-
-
-
-
-
-
-
-
1465
712
1390
685
1315
657
1204
623
1093
588
982
554
-
-
MED
1432
650
1381
628
1330
605
1279
583
1210
556
1140
529
1071
502
977
477
-
-
-
-
-
-
LOW
1191
527
1149
510
1107
494
1065
477
1009
459
952
441
-
-
-
-
-
-
-
-
-
-
042
HI
-
-
1681
797
1610
768
1540
740
1465
712
1390
685
1315
657
1204
623
1093
588
-
-
-
-
MED
1432
650
1381
628
1330
605
1279
583
1210
556
1140
529
-
-
-
-
-
-
-
-
-
-
LOW
1191
527
1149
510
1107
494
1065
477
-
-
-
-
-
-
-
-
-
-
-
-
-
-
048,060
HI
-
-
-
-
-
-
1908 1023 1832
982
1737
938
1656
889
1348
789
1252
754
-
-
-
-
MED
-
-
-
-
-
-
1773
894
1726
869
1674
852
1613
832
1339
731
-
-
-
-
-
-
LOW
-
-
-
-
1672
841
1610
804
1542
773
-
-
-
-
-
-
-
-
-
-
-
-
1. Above data includes allowances for a dry evaporator coil, gas heat exchanger and no filters. For additional pressure drops, refer to 
TABLE 9: BOTTOM SUPPLY AIR BLOWER PERFORMANCE
1
MODEL #
DNA
MTR
SPD
EXTERNAL STATIC PRESSURE - IWG
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
1.10
CF
M
 WA
T
T
S
CF
M
 WA
T
T
S
CF
M
 WA
T
T
S
CF
M
 WA
T
T
S
CF
M
 WA
T
T
S
CF
M
 WA
T
T
S
CF
M
 WA
T
T
S
CF
M
 WA
T
T
S
CF
M
 WA
T
T
S
CF
M
 WA
T
T
S
CF
M
 WA
T
T
S
030
HI
-
-
-
-
1115
454
1049
436
967
417
886
398
805
380
676
351
-
-
-
-
-
-
MED
895
300
853
289
811
278
769
267
697
252
-
-
-
-
-
-
-
-
-
-
-
-
LOW
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
036
HI
-
-
-
-
-
-
-
-
1458
688
1377
663
1295
639
1147
600
999
561
-
-
-
-
MED
1482
628
1428
613
1374
599
1320
584
1242
556
1163
528
1085
500
961
474
-
-
-
-
-
-
LOW
1239
510
1184
496
1130
481
1075
467
998
448
922
428
-
-
-
-
-
-
-
-
-
-
042
HI
-
-
1687
763
1614
737
1540
712
1458
688
1377
663
1295
639
1147
600
-
-
-
-
-
-
MED
1482
628
1428
613
1374
599
1320
584
1242
556
1163
528
1085
500
-
-
-
-
-
-
-
-
LOW
1239
510
1184
496
1130
481
1075
467
-
-
-
-
-
-
-
-
-
-
-
-
-
-
048,060
HI
-
-
-
-
-
-
1928
1032
1844
994
1636
923
1515
888
1441
849
-
-
-
-
-
-
MED
-
-
-
-
-
-
1805
837
1693
859
1580
819
1473
788
-
-
-
-
-
-
-
-
LOW
-
-
-
-
1725
850
1660
807
1557
776
1428
728
-
-
-
-
-
-
-
-
-
-
1. Above data includes allowances for a dry evaporator coil, gas heat exchanger and no filters. For additional pressure drops, refer 