Instruction manual GWV
55
gis
9
Starting and running
9.1
Introduction
Topics covered in this chapter, in sequence:
.
9.2
Starting and running
Start the appliance as follows:
1. Fill the appliance
.
2. Open
 the manual gas 
valve.
3. Switch on the power to the appliance using the 
isolator between the appliance and the power 
supply. 
4. Switch the electronic controller ON by setting the 
ON/OFF switch to position I.
The display will now show INTERNAL CHECK for 
about 10 seconds and go to the main menu.
5. Press the blue arrow once ( ) to position the 
cursor in front of ON and press 
. The 
display shown in the figure will appear.
6. Confirm the START OPERATION by pressing 
.
The appliance is now in "ON mode". If there is a 
heat demand, the appliance will run through the 
heating cycle
If the heating cycle is not run, there is no heat 
demand; if this is the case, Tset will probably need 
to be set
9.3
The appliance's heating cycle
The appliance's heating cycle is activated when the 
measured water temperature (T
3
) falls below the 
threshold value (T
set
). This set point value depends on 
the currently selected appliance operating mode. If the 
appliance is in the "OFF mode" (frost protection), for 
example, this value is 5°C. If the appliance is in the 
"ON mode", this set point can be selected, for 
example, 65°C.
The heating cycle runs successively through the 
following states:
1. HEAT DEMAND;
2. PRE-PURGE;
3. PRESSURE SWITCH;
4. PRE-GLOW;
5. IGNITION;
6. RUNNING 1;
7. RUNNING 2;
8. POST-PURGE.
The complete cycle is explained in the following 
example, which assumes the appliance is in the basic 
mode ON.
Note
The same heating cycle applies to the other 
operating modes.
INTERNAL CHECK
MENU
 »OFF
^ ON
È WEEK PROGRAM
GENESIS
IMD-0511 R1
a
a
 »START OPERATION
^ CHANGE SETPOINT
È
Tset=65ÉC
a