TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
63-2635—03
8
Fig. 16. Typical hookup of single transformer multistage 
system (up to 2H/2C).
Fig. 17. Typical hookup of dual transformer multistage 
system (up to 2H/2C).
Heat Pump System Wiring
Fig. 18. Typical hookup of single-stage heat pump with no 
auxiliary heat (1H/1C).
Fig. 19. Typical hookup of multistage heat pump with no 
auxiliary heat (2H/2C).
M23016
HEAT RELAY 2
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
FAN RELAY
POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND 
OVERLOAD PROTECTION AS REQUIRED. 
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION 
IS OPTIONAL.
1
3
2
3
COOL RELAY 1
HEAT RELAY 1
COOL RELAY 2
L1 
(HOT)
L2
1
24 VAC
ECONOMIZER
C
G
Y
W
RC
R
W2
Y2
A
S1
S2
2
M23017
HEAT RELAY 2
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
FAN RELAY
POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND 
OVERLOAD PROTECTION AS REQUIRED. 
REMOVE FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION 
IS OPTIONAL. WHEN USED, THE COMMON MUST CONNECT 
TO THE COOLING TRANSFORMER SECONDARY.
1
3
2
3
COOL RELAY 1
HEAT RELAY 1
COOL RELAY 2
L1 
(HOT)
L2
1
24 VAC
L1 
(HOT)
L2
1
24 VAC
ECONOMIZER
C
G
Y
W
RC
R
W2
Y2
A
S1
S2
2
COOLING
TRANSFORMER
HEATING
TRANSFORMER
COMPRESSOR CONTACTOR
M23018
CHANGEOVER VALVE
1
2
3
4
5
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD 
PROTECTION AS REQUIRED. 
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION 
IS OPTIONAL.
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" 
IN THE INSTALLER SETUP.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. 
WIRES MUST HAVE A CABLE SEPARATE FROM THE 
THERMOSTAT CABLE.
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
L1 
(HOT)
L2
1
24 VAC
5
ECONOMIZER
C
G
Y
O/B
RC
R
W1
Y2
A
S1
S2
4
2
COMPRESSOR 1
COMPRESSOR 2
M23019
CHANGEOVER VALVE
FAN RELAY
1
2
3
4
5
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD 
PROTECTION AS REQUIRED. 
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION 
IS OPTIONAL.
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" 
IN THE INSTALLER SETUP.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. 
WIRES MUST HAVE A CABLE SEPARATE FROM THE 
THERMOSTAT CABLE.
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
3
L1 
(HOT)
L2
1
24 VAC
5
ECONOMIZER
C
G
Y
O/B
RC
R
W1
Y2
A
S1
S2
4
2