Honeywell T7984 A 사용자 설명서

다운로드
페이지 8
T7984 A,B,C ELECTRONIC MODULATING CONTROL THERMOSTATS 
Output 2 On/Off (T7984B only) 
A 24 Vac on/off output which is normally used to control terminal 
reheat in a zoned system. Example: electric base board relay, 
electric duct heater relay, perimeter on/off 24 Vac valve, etc. 
This output can also be used for cooling applications with the 
mode jumper installed (See the control curves for T7984B) 
There is a status LED mounted internally that indicates the 
action of the output. The red LED indicates that the output 
electronic contact (triac) is energized. 
This electronic contact (triac) is rated at 1.1A max. in rush and 
0.5A running. This electronic contact (triac) is protected with a 
PTC self-resetting fuse. In the event of an overload or a short 
circuit, the PTC self-resetting fuse will reduce the load to a 
very low level. If the power is removed or the overload or the 
short disappears, the PTC fuse will return to its normal state 
and allow normal operation. 
CPH (Cycles per Hour) 
It is possible to fix the number of time per hour the reheat end 
device will be energized. Those settings are adjusted with DIP 
switch (S1). 
Two different settings are possible: 
4 cycles per hour or 8 cycles per hour 
Use the following setting for the following reheat device applications: 
Table 5. Cycle settings for reheat device applications 
4 cycles per hour 
8 cycles per hour 
Anything using a gas fired or 
oil fired terminal reheat device 
N.C. 24 Vac thermal valve 
(Hot wax thermal body valve) 
Any gear driven end device 
valve or damper actuator 
Properly sized electric base 
board strip 
Oversized capacity electric 
base board strip 
Properly sized electric duct 
heater 
Oversized capacity electric 
duct heater 
Output 2, Modulating Analog Output 2 to 
10Vdc (T7984C only) 
A modulating signal that uses a variable Vdc signal for the 
control of analog valve actuator or SCR power controller 
which is normally used to control terminal reheat in a zone 
system. 
This type of output on the T7984C uses a half wave rectifier 
bridge. If the same transformer is to be used for the 
thermostat and the end device, be sure to select end devices 
which also use a half wave rectifier bridge. 
There is a status LED mounted internally that indicates the 
action of the output. The red LED intensity is proportional to 
CHECKOUT 
Service LED 
All thermostats have internal service LED & a system status 
Led on the cover. The internal service LED are colored lights 
that can be viewed from the side of the thermostat they are 
energized and the system status LED is the one mounted on 
the cover. (See the checkout & start up procedures section.) 
Table 6. System Status LEDs 
Thermostat operation can be confirmed with the System 
status LED on the thermostat cover. 
Model 
Color 
Explanation 
T7984A 
green  High intensity = Demand for cooling or 
heat. 
Low = no demand. 
T7984B,C  red 
Flashing = Night setback/set-up 
activated. 
Table 7. Internal Service LEDs 
C  Color 
Indication when 
• 
• 
•  green  Intensity is proportional to output 1 
• 
red 
On/off output 2 is closed (load 
energized) 
•  red 
Intensity is proportional to reheat 
output 
Test Condition: 
1.   No contact changeover input and changeover sensor 
disconnected. No wire on mode input. 
2.   T7984B & C: set DIP switch S3 and S4 to —ON“ position 
to remove 75°F (24°C) limitation. 
3.   Room termperatures must be between 60-80°F. 
Table 8. Knob position 
Rotate Knob to:  Green 
Red (reheat models only)
T7984B & C 
Minimum Position  ON 
OFF 
Maximum Position  OFF 
ON 
The night setback feature can be temporarily overridden for 2-
1/2 hours by depressing the override button on the thermostat 
cover. 
the action of the output. 
Automation and Control Solutions 
Honeywell International Inc. 
1985 Douglas Drive North 
Golden Valley, MN  55422 
customer.honeywell.com 
Honeywell Limited-Honeywell Limitée 
35 Dynamic Drive 
Scarborough, Ontario  M1V 4Z9 
® U.S. Registered Trademark 
© 2005 Honeywell International Inc. 
95C-10815–2    M.S.  Rev. 09-05