TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
13
62-0273—05
OPERATION
Fan Sequence Operations (ISU 347, 348, 
349)
If heat pump or conventional application modes are 
enabled in ISU 170, then ISU 347 is not available for fan 
ramp algorithm. The fan operates as a default ON/AUTO 
selection that works the same way as our 
CommercialPRO TB7220 thermostat. There is only one 
fan relay output that is activated.
If PTAC or fan coil thermostat application modes are 
enabled in ISU 170, then ISU 347 is available for installer 
setup selection.
The thermostat comes factory default with the fan 
ramping algorithm enabled (ISU 347). This gives the user 
the ability to select Auto-Lo-Med-Hi option in ISU 348 or 
Auto only option in ISU 348. Auto sets the thermostat into 
the fan ramping algorithm mode and automatically sets 
the sufficient speed for PI control. Auto also automatically 
shuts the fan off when there is not a call for heating or 
cooling. If the user decides to disable ISU 347, then the 
fan will only have Lo-Med-Hi option available.
If ISU 347 is not enabled, then ISU 348 does not appear 
as a user selection choice.
If ISU 347 is enabled, then ISU 349 is available as a 
selection choice. The user can select either a 2 hour or 4 
hour timer fan reset function. The fan will reset from a 
constant speed to auto mode after the time period 
expires. If ISU 347 is not enabled, then ISU 349 does not 
appear as a user selection choice.
Equipment Sequence Operations (ISU 
170)
Heat Pump and Conventional
Heat Pump and conventional use a single fan speed. The 
single fan speed label will be G, located on the G1 
terminal relay output. Label should read G/Gl to help out 
the installers. Display on the thermostat for these modes 
will give the Fan On/Auto option. There is no fan ramping 
algorithm, ISU 347, 348, 349 are not available.
PTAC
PTAC modes 10 and 11 will have the same selection 
options available as the heat pump selection options. The 
only difference is that the PTAC options have a Lo and Hi 
speed fan output instead of single speed output and that it 
follows the fan sequencing described above with ISU 347, 
348, 349.
4 Pipe
4 pipe is treated similar to 1H/1C conventional. It follows 
the fan sequencing described above with ISU 347, 348, 
349.
2 Pipe
There are two different 2 pipe modes - 2 pipe only and 
pipe with reheat
.
2 pipe only - 2 pipe modes do not contain the ability to 
have automatic changeover. They are manual 
changeover only. The thermostat will have a priority when 
choosing a system mode (heat or cool). When ISU 340 
has a 2 pipe changeover sensor enabled, the thermostat 
screen system mode will lock on heat or cool (whatever 
the changeover sensor is communicating to the 
thermostat). If ISU 340 does not have a changeover 
sensor enabled, then the system mode from the 
thermostat screen can manually be adjusted between 
heat or cool. It follows the fan sequencing described 
above with ISU 347, 348, 349.
2 pipe with reheat - 2 pipe modes do not contain the 
ability to have automatic changeover. They are manual 
changeover only. The thermostat will have a priority when 
choosing a system mode (heat or cool). When ISU 340 
has a 2 pipe changeover sensor enabled, the thermostat 
screen system mode will lock on heat only. When the 2 
pipe changeover sensor is sensing cool mode, the user 
can adjust to heating mode which will bring on the 
auxiliary heat. If ISU 340 does not have a changeover 
sensor enabled, then the system mode from the 
thermostat screen can manually be adjusted between 
heat or cool. It follows the fan sequencing described 
above with ISU 347, 348, 349.
Special Programmable Mode Functions
Installer Setup 160 allows the thermostat to be configured 
for either a mode with a programmable 7 day schedule or 
as a non-programmable thermostat.
Preoccupancy purge (ISU 185) 
This feature is available only when the thermostat is 
configured as a programmable schedule and when a fan 
is used. The fan will run 1-3 hours before the occupied 
schedule starting time to circulate air.
Override Button, Temporary Override (Duration Limit 
ISU 535)
While in the programmable schedule mode, an override 
button is available to perform temporary override control. 
The default override time can be configured through ISU 
535. Lockout configuration via ISU 670 can provide 
restrictions on access to setpoint changes, system 
changes, and schedule changes.
No remote setback
The remote setback feature only works in the non-
programmable mode.
Special Non-Programmable Mode 
Functions
Override (Optional)
The override feature is optional in the non-programmable 
mode. The override can be configured through ISU 342. 
When the override is activated in the non-programmable 
mode it will temporarily override to a new setpoint until the 
end time expires.
Remote Setback
Remote Setback is available (ISU 340). Occupancy 
sensors, manual time clock inputs, and DDC night 
setback can be used to provide inputs to setback the 
thermostat. Unoccupied heating (ISU 343) and 
unoccupied cooling (ISU 346) setpoints are available to 
configure the setback setpoints.