TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
9
62-0273—05
INSTALLER SETUP NUMBERS, SETTINGS, AND TESTS (TABLE 4)
Configure Installer Setup
1. Press and release the System key.
2. Press System and Done keys simultaneously.
3. Hold keys for approximately five seconds, until the 
screen changes.
4. When the display changes, release the System and 
Done keys.
NOTE: See Table 4 for installer setup (ISU) numbers 
and settings.
Installer System Tests
Use the Installer System Test section to test the heating, 
cooling and fan. Refer to the latter portion of Table 4.
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed 
during Installer System Test
Avoid cycling compressor quickly.
IMPORTANT
Use Installer System Test to test heating, cooling 
and fan. The setting chosen for System Type 
(Installer Setup Number 0170) can prevent some 
System Test Numbers from appearing.
Table 4. Installer Setup Menu.
Installer
 Setup 
Number
Installer Setup 
Name
Default 
Setting
All Settings
Notes
0120
Date (Year Upper)
20
20—21
Available year range: 2001 - 2178
0130
Date (Year Lower)
08
00-99
Available year range: 2001 - 2178
0140
Date (Month)
6
1-12
0150
Date (Day)
15
1-31 (Month Dependent)
0160
Schedule Options
4
0—Non-Programmable
4—Programmable
0170
System Selection
1
1—1H/1C Conv
2—1H w/o fan
3—1H with fan
4—1C
5—1H/1C HP
6—2H/1C HP
7—4 pipe Fan Coil
8—2 pipe Fan Coil
9—2 pipe Fan Coil w/ Aux 
Heat
10—PTAC 1H/1C (Hi 
speed, Lo speed Fan)
11—PTAC 2H/1C (Hi 
speed, Lo speed Fan)
Relay Y is used for 2 pipe fan coil output relay.
0180
Heat Fan Operation 0
0—Fossil
1—Electric
Only shows up if conventional system with heat 
stages and fan capability is selected (ISU 0170). If 
heat pump is selected, fan defaults to electric. If 
fan coil or PTAC modes are selected, fan defaults 
to electric (does not show up).
0185
Pre-occupancy 
Purge Duration
0
0—no duration
1—one hour
2—two hours
3—three hours
Shown only if system has fan and schedule is 
programmable (ISU 0160).
Pre-occupancy purge is enabled by a nonzero 
duration.
0190
Reversing Valve 
O/B
0
0—O (O/B On Cool)
1—B (O/B On Heat)
Only shown if heat pump or PTAC system is 
selected.
0220
Cycles Per Hour 
(CPH) for first stage 
cooling/compressor
3
1-6
Only shown if system has cool stages (ISU 0170). 
Shown for heat pump, fan coil, PTAC, and 
conventional cooling stages.
0240
CPH for first stage 
heat
5
1-12
Only shown if system is conventional with heat 
stages, 4 pipe fan coil, 2 pipe fan coil (ISU 0170).
0270
CPH for Em Heat
9
1-12
Only shown if HP with reheat, 2 pipe fan coil with 
reheat, and PTAC with reheat (ISU 0170).
0280
Continuous 
Backlight
0
0—No
1—Yes
Always shown; however, if AC power is not 
present, the option is overridden and normal 
backlight operation occurs.