Maintenance Object Repair Procedures 
9-42
ALARM-PT (ALARM PORT) 
9
Station Status and Translation Audits and 
Updates Test (#36)
For an analog line port that is administered as an external alarm, this test is 
limited to updating the software with the switchhook state. 
Table 9-17.
TEST #35 Battery Feed Test 
Error 
Code
Test 
Result
Description/Recommendation
ABORT
Could not allocate the necessary system resources to run this test. 
1. Retry the command at 1-minute intervals for a maximum of 5 times.
1000
ABORT
System resources required to run this test are not available. The port may be 
reporting an external device alarm. 
1. Enter test external-device-alarm port UUCSSpp to determine if the port 
is reporting an EXT-DEV failure before retesting.
2. When the port has no EXT-DEV failure, retry the command at 1-minute 
intervals for a maximum of 5 times.
1004
ABORT
The port received an EXT-DEV failure during the test. The test has been 
aborted.
1. Enter test external-device-alarm port UUCSSpp to determine if the port 
is reporting an EXT-DEV failure before retesting.
2. If the port has no EXT-DEV failure, retry the command at 1-minute 
intervals for a maximum of 5 times.
2000
ABORT
Response to the test request was not received within the allowable time 
period.
2100
ABORT
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals for a maximum of 5 times.
FAIL
The port’s battery feed chip is unable to supply sufficient power to sense the 
external device alarm. This may occur when the test is performed at the same 
time that the external device contact closure occurred.
1. Enter test external-device-alarm port UUCSSpp to determine if the port 
is reporting an EXT-DEV failure before retesting. Wait until the port has no 
EXT-DEV failure before retesting. 
2. Retry the command at 1-minute intervals for a maximum of 5 times.
PASS
The port’s battery feed chip is able to provide power to the external device 
alarm to detect contact closure. 
Continued on next page