Mounting and installing 
3.1 Installation 
place 
The location of the XP-COMPACT must be driven by the following criteria: 
− Protection 
from 
unauthorized handling 
−  Dry dust free room, no condensation 
−  Never install directly over the battery and never in a cabinet together with the 
batteries 
−  Keep ventilation holes free  
−  In mobile installations it is important to keep the vibrations down as low as 
possible 
3.2 Fixing 
3.2.1 Fixing the XP-COMPACT 
Basically the XP-COMPACT can be installed in any desired location. Preferred is that 
the appliance be wall mounted with battery cables downwards. The XP-COMPACT is 
fixed on the wall with four screws through the four holes (diameter 5.5mm) which are 
accessible from the outside. In motor vehicles XP-COMPACT must be fixed on 
vibrations reducing elements. The XP-COMPACT must not be fixed on a combustible 
base, as the back of the casing can get hot and reach up to 80 degree Celsius. 
3.2.2  Protection cover IP-23 
This cover IP23 (Order ref. CIP-23) can be easily 
installed after the fixation of the XP-COMPACT. For that 
release a little the too screws down and more the tow up. 
Then it’s possible to pass the IP 23 cover between the 
XP-COMPACT and the wall. The cover must touch the 
screws. Lock on the four screws, it’s ready. 
3.3 Connections 
3.3.1  General instructions on connecting 
−  The cable connection on the terminals AC INPUT / AC OUTPUT / 16A 230VAC 
are carried out with a screwdriver Nr.1 and the connection on the SOLAR 
terminal with a screwdriver Nr.2. 
−  The conductor cross section on the terminals AC INPUT / AC OUTPUT / 16A 
230VAC of the connecting cable must be minimum 2.5mm2. 
−  All connecting cables and also the mounted battery cables, must be fixed with 
strain relief clamps. 
−  The XP-COMPACT is delivered with battery cables already connected. 
−  The battery cables must never be extended. If the extension is unavoidable then 
the conductor cross section must be elevated accordingly. 
−  To protect the battery cable, a fuse corresponding to the conductor cross 
section must be fixed directly on to the battery. 
−  All cables must be tightly screwed in place. For safety, a yearly control is 
recommended. In mobile installations control must be carried out more often. 
−  Connecting must be done by qualified personnel. Material such as cable, 
connectors and distribution boxes, fuses etc. used in the installation must 
comply with the respective valid low-voltage installation rules and regulations.