2.4.3 
Scanner Chassis Grounding Jumper Settings 
 
The scanner chassis grounding method can be selected by positioning a jumper (see 
Figure 9). In this way the scanner chassis can be connected to earth ground (only if 
pins 7 or 8 are connected to a good earth ground) or to the power supply ground 
signal. The scanner chassis can also be left floating but, in this case, the jumper 
must be removed. 
 
 
 
Figure 9 – Chassis Grounding 
 
 
 
2.4.4 Scanner 
Selection 
 
 
DS1100 
DS2200 
 
Other Devices 
 
 
 
floating 
to EARTH 
GROUND
(default) 
to GND 
Figure 10 - Scanner Selection Switch 
 
 
This switch must be set upward only when a DS1100 or a DS2200 scanner (10-30 V 
version) is connected. For all the other devices the switch must be set downward. 
 
 