Network Management Card & Modbus/Jbus                                                                                        34022321XT indice :AE            Page 95/98 
Network Management Teleservice Card 
                 
APC by Schneider Electric  
www.apc.com 
If the Environment Sensor is detected , the following information are managed. 
upsmgEnvironAmbientTemp 
0.1 degré 
{8,1,0} 
upsmgEnvironAmbientHumidity 
0.1 % 
{8,2,0} 
upsmgEnvironmentNum 
 
{8,6,0} 
upsmgEnvironmentIndex 
 
{8,7,1,1,1 } 
upsmgEnvironmentComFailure 
1(yes)  2(no) 
{8,7,1,2,1} 
upsmgEnvironmentTemperature 
0.1 degré 
{8,7,1,3,1} 
upsmgEnvironmentTemperatureLow 
1(yes)  2(no) 
{8,7,1,4,1} 
upsmgEnvironmentTemperatureHig
1(yes)  2(no) 
{8,7,1,5,1} 
upsmgEnvironmentHumidity 
0.1 % 
{8,7,1,6,1} 
upsmgEnvironmentHumidityLow 
1(yes)  2(no) 
{8,7,1,7,1} 
upsmgEnvironmentHumidityHigh 
1(yes)  2(no) 
{8,7,1,8,1} 
upsmgEnvironmentInput1State 
closed(1), open(2) 
{8,7,1,9,1} 
upsmgEnvironmentInput2State 
closed(1), open(2) 
{8,7,1,10,1}