PMCM-ETHCC-0208 
ACCESS 9340 and 9360 Meter Ethernet Communications Card
2/2008
Introduction
© 2008 Siemens Energy & Automation, Inc.. All Rights 
3
EN
G
L
IS
H
Meter Firmware
Before installing the 9340-60-ETHER module, the host ACCESS 9340 or 
9360 must be running firmware version 10.6 or higher. To verify you have 
the correct firmware version, do the following:
1. From the meter display, press MAINT > DIAG > METER.
2. Verify that the number before OS, RESET, and DL is 10.600 or higher.
To download the latest firmware version, go to 
www.sea.siemens.com/access, select “ACCESS 9340/9360 Power Meter” 
from “Compact Power and Energy Meter” and then click the firmware file 
you want to download. 
NOTE: To install the firmware upgrade you will need the Download 
Firmware Upgrade Utility (DLF3000), which is provided on the 
9340-60-ETHER module Technical Library CD-ROM. If you do not have the 
CD-ROM, you can download DLF3000 from the downloads page, then 
follow the installation instructions. If you need assistance using DLF3000, 
refer to the Help file included with DLF3000.
Additional Resources
9340-60-ETHER module Documentation: Go to 
www.sea.siemens.com/access, select “ACCESS 9340/9360 Power Meter” 
from “Compact Power and Energy Meter” and then click the manual you 
want to download.
For installation instructions and hardware specifications, see the 
9340-60-ETHER module installation manual PMIM-ETHCC-0208.
9340-60-ETHER module Firmware: See “Firmware” on page 27 to learn 
where to download firmware updates and how to install new firmware.