Schneider Electric 66123 사용자 설명서

다운로드
페이지 98
 
 
Network Management Card & Modbus/Jbus                                                                                        34022321XT indice :AE            Page 76/98 
Network Management Teleservice Card 
                 
APC by Schneider Electric  
www.apc.com 
10.3  Modbus register map 
10.3.1 Detailled status table  
Status description 
Status to 0 
Status to 1 
Word 
hex 
Bit 
0 - F 
Status Familly 
for 
BMS design 
Load powered  
(protected or not protected) 
No 
yes 
40 
Status 
Load on inverter  
(UPS on AC normal or on Battery and Q5N closed) 
No 
yes 
40 
Status 
UPS general alarm – UPS HMI Led Red  (Nota 8)  
No 
yes 
40 
Major Fault 
UPS on Battery (Nota 5) 
No 
yes 
40 
Status 
Low Battery Warning (Nota 5) 
No 
yes 
40 
Major Warning 
End of Battery Runtime (Nota 5) 
No 
yes 
40 
Major Fault 
Load on bypass  
No 
yes 
40 
Status 
Communication fault 
absent 
present 
40 
Major Fault 
UPS overload 
No 
yes 
40 
Major Warning 
Emergency stop 
absent 
present 
40 
Major Fault 
Battery to be checked  
or External battery monitoring fault (Nota 5) 
No 
yes 
40 
Minor Fault 
 
Device ventilation fault (Nota 6) 
No 
yes 
40 
Major Fault 
41 
Setting 
41 
Setting 
UPS type (Nota 4) 
0, 5, 6 : undefine, 
1 : Unitary, 
2 : Modulare,  
3 : parallel: 
4 : SSC 
41 
Setting 
Manual bypass switch (Q3BP) 
Open 
Closed 
41 
Status 
Rectifier major failure (Nota 5) 
No 
Yes 
41 
Major Fault 
Load not protected in unitary  
Load not protected in parallel (external Q5N) 
No 
Yes 
41 
Major Fault 
UPS in Power Saving Mode (Nota 9) 
No 
Yes 
41 
Status 
UPS HMI Orange Led - (Nota 8) 
No 
Yes 
41 
Major Warning 
Battery present (Nota 5)  
absent 
present 
42 
Setting 
Battery test in progress  (Nota 5) 
No 
yes 
42 
Status 
Battery over temperature (Nota 5) 
No fault 
Fault  
42 
A  
Major Fault 
Battery circuit breaker (QF1) (Nota 5) 
Open 
Closed 
42 
Status 
AC Normal switch (Q1) 
Open 
Closed 
44 
Status 
AC Normal voltage out of tolerance (Nota 5) 
No 
yes 
44 
Major Warning 
Rectifier (PFC)  fuse fault (Nota 5) 
No 
yes 
44 
Major Fault 
AC Normal frequency out of tolerance (Nota 5) 
No 
yes 
44 
Major Warning 
Redundancy lost for parallel 
No 
yes 
45 
Major Warning 
K2S fault (Nota 7) 
No 
yes 
45 
Minor Fault 
K2S state (Nota 7) 
No 
yes 
45 
Status 
Overlaptransfert fault on SSC 
No 
yes 
45 
Minor Warning 
UPS on Maintenance position 
No 
yes 
46 
Status 
AC bypass overload (Nota 7) 
No 
yes 
46 
Major Warning