APC 6000 사용자 설명서

다운로드
페이지 38
Page 28 - 
6739389EN/FB
System information
Message format
This section describes the
messages exchanged between the
"GTC link" communication interface
and the external computer based
on the JBUS protocol.
The length of time after which a
message must be interpreted as
"not understood" depends on the
type of command sent.
The table opposite lists maximum
response times:
Data rate
1200 
Baud
2400 
Baud
4800 
Baud
9600 
Baud
status information only
0,5 s
0,25 s
0,12 s
0,06 s
all measurements
2 s
1 s
0,5 s
0,25 s
Response time of event (independent of data rate)
- inverter start-up and connect
:
30 s
- rectifier-charger startup
:
30 s
- rectifier-charger or inverter stop
:
30 s
For the "responses", refer to the
"JBUS protocol" section function 1
and 3.
Example of read data array commands sent by the terminal
(address: 20H)
request
station
function
data
length
CRC 16
code
address
read voltage
20
03
0140
0015
82 9C
array
(21 values)
read current
20
03
0100
000F
28 03
array
(15 values)
read global
20
01
04C0
000B
7A 70
state bits
(11 bits)
command
station
function
bit
data
not
CRC 16
code
address
used
charger on
20
05
0C00
FF
00
89 DB
charger off
20
05
0C01
FF
00
D8 1B
inverter on
20
05
0C04
FF
00
C8 1A
inverter off
20
05
0C05
FF
00
99 DA
Sample commands
List of variable fields
(same for all cubicle types)
The binary data and binary
commands can be accessed bit or
word-wise.
The word address and position of
the bit in the word can be
determined from the bit address:
◗ 
 hundreds and tens digit of bit
address = word address;
◗ 
 least significant digit of bit
address = bit position.
JBUS fields
address in hexadecimal
access
start
end
signaling
0
5
read / write
signaling
6
F
read
binary data
40
BF
read
commands
C0
DF
read / write
counters
E0
FF
read
currents
100
13
read
voltages
140
17
read
powers
180
19F
read
frequencies
1A0
1BF
read
battery
1C0
1DF
read
adjustments
200
2FF
read
maintenance
300
3FF
read