Siemens PANEL PC 877 사용자 설명서

다운로드
페이지 288
Application planning 
 
4.4 Mounting Positions and Fastening 
 
SIMATIC Panel PC 877 
4-8
 
Operating instructions, Release 07/2006, A5E00877780-01 
4.4.4 
Protection against dust and water 
Principle 
The degree of protection provided at the front is assured when the mounting seal lies 
completely against the mounting cut-out.  
 
 
Caution 
Please ensure that the material strength at the mounting cut-out is a maximum of 6 mm. 
Please follow the specifications for the dimensions in the "Mounting cut-out" section. 
The degrees of protection are only guaranteed when the following is observed: 
• 
The material strength at the mounting cut-out is at least 2 mm. 
• 
The surface plane deviation of the mounting cut-out in relation to the external dimensions 
of the control unit amounts to ≤ 0.5 mm when the control unit is mounted. 
 
IP65 degree of protection and NEMA4 
IP65 degree of protection and compliance with the NEMA4 regulations are only ensured 
when clamp mounting together with a ring seal.  
IP54 degree of protection 
This degree of protection is achieved for screw fixing of all operator control units with a key 
front panel and the 15" and 19" operator control units with a touch front panel. This degree of 
protection is assured for the 19" operator control unit with a touch front panel when the 
mounting components for 19" rack accessories are used.  
 
 
Note 
For screw fixing of the 19" touch panel front, a backing plate is available as an accessory. 
For further information, see "http://mall.ad.siemens.com/".