2. Installation
2.6 Required protective devices and cable cross-sections
Recommended upstream protection
   
  
Recommended downstream protection
  
Required cable cross-sections
 Terminal-block cable capacity: 6 mm
2
, solid or stranded wire (maximum 8 mm
2
 or AWG 8).
 
Capacity for earthing conductor: 6 mm
2
, solid or stranded wire (maximum 8 mm
2
 or AWG 8).
UPS power rating
Upstream circuit breaker
The indicated protection ensures 
discrimination for each output circuit 
downstream of the UPS.
If these recommendations are not followed,
 
protection discrimination is not achieved and 
may result in a potential power interruption to 
the connected devices.
4000 RT
D curve - 32A
5000 RT
D curve - 32A
  
UPS power rating
Downstream circuit breaker
The indicated protection ensures 
discrimination for each output circuit 
downstream of the UPS.
If these recommendations are not followed,
 
protection discrimination is not achieved and 
may result in a potential power interruption to 
the connected devices.
4000 RT
Z curve - 10A
C curve - 4A
5000 RT
Z curve - 10A
C curve - 6A
G     N      L
N
L
2 poles circuit breaker 
To UPS Normal AC source