5. Troubleshooting
5.1 Troubleshooting LEDS (21) and (22)  
5.2 Troubleshooting not requiring MGE UPS SYSTEMS after-sales support 
  
  
  
 
 If 
LED 
(21) is ON:
the equipments are protected by the UPS 
but the operation is downgraded.
 
 If 
LED 
(22) is ON:
the equipments are no longer protected 
by the UPS.
 
 
Press the escape button (24) to stop the 
audible alarm.
Note : 
In case of 
"
MULTIPLE FAULT
"
, press the 
"
Enter
"
 button (27) and the scroll button (25) 
to get access to further details.
In case of 
"
LCM WARNING
"
, refer to LCM 
section (see section 6).
 
 
Press the 
"
Enter
"
 button (27) to display the details below :
Displayed details
Signification
Correction
 
NO BATTERY
The battery is incorrectly connected
Check battery connections
I/O BAD CONNECTION
AC source is not connected to the correct 
terminals
Check AC wiring
NO POWER MODULE
The power sub-module is not inserted
Check power sub-module connections (see 
section 7.1)
NO BATTERY MODULE
The battery sub-module is incorrectly 
connected
Check battery connections (see section 7.2)
INV THERM OVERLOAD
The UPS shuts down automatically because 
of a major overload.
Check the power drawn by the connected 
devices and disconnect any non-priority 
devices.
INVERT LIMITATION
Short circuit conditions on output devices
Check the installation at the UPS output 
(wiring, fault equipment)