MGE UPS Systems 4000 RT 사용자 설명서

다운로드
페이지 38
34008030EN/AA
 - Page 33
7. Maintenance
Reconnecting the battery sub-module :  
7.3 Maintenance on a UPS equipped with the ModularEasy MX module  
  
 
Carry out the above instructions in reverse order.
 To ensure safety and high performance, use only batteries supplied by MGE UPS SYSTEMS.
 
Before any action on the manual bypass (61) located on the ModularEasy module front panel, always check that the 
inverter is stopped (press the "0" button more than 3 seconds).
The equipments should be powered via the Normal AC source, and not protected by the UPS. 
 
 The 
ModularEasy module makes possible to 
service or even replace the UPS without 
affecting the connected equipments 
(HotSwap function).
Maintenance: 
1 - Set the manual bypass (61) to the Bypass 
position.
The equipments are supplied directly with 
Normal AC source.
2 - Check the UPS main bezel and wait the 
LCD stops (30 seconds). 
3 - Padlock the manual bypass (61) on 
bypass position.
4 - The UPS can now be disconnected and 
replaced.
Return to normal operation:
5 - Properly wire the UPS (see section 2), and 
connect internal batteries.
6 - Set the manual bypass (61) to the Test 
position then to Normal position : the 
equipments are powered via the Normal AC 
source, but not protected by the UPS..
7 - Push the 
"
I
"
 button (29) till the buzzer 
beeps. LED (20) is ON, and LEDs (30)(32) 
and (34) (see page 9) are green: the 
equipments are protected by the UPS.
Test position:
It is also possible to fully test the UPS before 
the manual bypass (61) is set on Normal 
position.
To check the UPS, after step 5, follow this 
operating method:
6bis - Set the manual bypass (61) to the test 
position.
7bis - Push the 
"
I
"
 button (29) till the buzzer 
beeps. After UPS Internal test, LED’s (30)
(32) and (22) should be ON: no failure has 
been detected.
To return to normal operation:
 Push the "0" button (28) more than 3 
seconds.
 Then follow the operating method from step 
6.
TEST
BYP
ASS
NORMAL
61
TEST
BYP
ASS
NORMAL
1
3
ESC
I
O
32
30
29
TEST
BYP
ASS
NORMAL
6
7
34