Example of setting>
 
The example below shows how to configure the local/remote operation.
 
 
F terminal ............... Operating command 
R terminal ............... EtherNet/IP-
Modbus TCP
 local/remote   
(Terminal in this example) switching 
VIA terminal ........... Operation frequency command 
 
<Wiring>
 
   
VF-MB1
 
F
 
R
 
CC
 
PP 
VIA
 
Variable resistor for adjustment
10k ohm
EtherNet/IP-Modbus TCP 
/local Switch
Operation command
SINK
SW1*
 
SOURCE
CC
 
PLC
 
<Parameter setting>
 
cmod
(Command mode selection) = 0 (Terminal board)
 
fmod
(Frequency setting mode selection 1) = 1 (VIA)
 
f112
(Input terminal selection 2 (R)) = 48 (Remote/Local control)
 
 
<Operation>
 
R-CC terminal open: VF-MB1 is controlled as a slave device of the EtherNet/IP™ - 
Modbus
®
 TCP.
 
R-CC terminal closed: 
F-CC terminal short to RUN 
F-CC terminal open to STOP 
Output frequency is set up by the VIA signal input. 
 
(Note)
   
When the local(HAND) / remote key (f750=2) is chosen as EASY key selection and 
the EASY key lamp of an inverter front panel is on, priority is most given to operation by 
a panel. (Refer to the inverter instruction manual for details).