Chassis Installation/Placement
Page 2-3
Chassis Installation/Placement
The IntraCore 8000 can be installed in a standard 19-inch equipment rack. It 
can also be placed on a stable horizontal surface.
I Important: The equipment rack or desk on which you 
install your IntraCore 8000 must be secure and stable. 
Equipment racks must be fastened to the floor; desks 
must be resting on a flat, stable surface.
Installation in an Equipment Rack
To install the unit in an equipment rack, use the following procedure.
Safety Precautions for Rack Installation
I Important! Before continuing, disconnect all cables 
from the IntraCore 8000. Also, do not install any optional 
modules you have purchased until the switch has been 
installed in the rack.
Equipment Rack Guidelines
Table 2-2    Equipment Rack Guidelines
Guideline
Specification
Size
Width; 17.75 inches (45.09 cm).
Depth: 19.25 inches (48.9 cm) to 32 inches (81.3 cm).
Stability
Rack must be bolted to the floor. Mount heavier units at the bottom of the 
rack. If the IntraCore 8000 is the only unit,  mount it the bottom of the 
rack..
Ventilation
Ensure that the rack is installed in a room where the temperature remains 
below 40° C (104° F). Ensure also that there are no obstructions, such as 
other equipment or cables, blocking airflow to or from the IntraCore 8000 
vents. 
Clearance
In addition to providing clearance for ventilation, ensure that there is ade-
quate clearance for servicing the modules of the IntraCore 8000 from the 
front.