CHAPTER 2 Connected Information 
2.3 Power cable connection 
23 
C122-H007-01EN 
 
100  V  Redundant  Power Feed Configuration  (Single power feed,  Redundant Power 
Feed) 
It is necessary to arrange four PSUs, two FANUs and four power supply cables (100 V NEMA 5-15P) for 
100V redundant power feed configuration (single power feed, redundant power feed). 
 
FIGURE 2.14 100V Redundant Power Feed Configuration (Single power feed, Redundant Power Feed) 
 
 
Number 
Description 
(1) 
Distribution Panel AC100V AC#0system 
 
Standard  Configuration of 200 V (single power feed, no  redundant power feed) with 
Power Distribution Box Connection 
It is necessary to arrange two PSUs, four FANUs, two power cables (200 V IEC60320 C20) and two power 
distribution boxes (200 V IEC60320 C19×3type) for standard configuration of 200 V (single power feed, no 
redundant power supply).  
When the power distribution box is used, it is necessary to secure the breaker characteristic of distribution 
panel. See “
.” 
 
FIGURE 2.15 Standard Configuration of 200 V (single power feed, no redundant power feed) with Power 
Distribution Box Connection 
 
Number 
Description 
(1) 
Power distribution box (200V C 19 
 3 type)