Code
Name/Description
Adjustment range
Factory setting
I_O-
Input Output menu
tCC
M Type of control
2C
2C
3C
v
)
The open or closed state of the input controls the running or stopping.
Example of "source" wiring:
Example of "source" wiring:
LI1: forward
LIx: reverse
LIx: reverse
v
)
"forward" or "reverse" pulse is sufficient to command starting, a "stop" pulse is sufficient to command
stopping
Example of "source" wiring:
stopping
Example of "source" wiring:
LI1: stop
LI2: forward
LIx: reverse
LI2: forward
LIx: reverse
DANGER
UNINTENDED EQUIPMENT OPERATION
When this parameter is changed,
2 wire type control
tCt
page
and all the assignments involving the logic
inputs will revert to their default values.
Check that this change is compatible with the wiring diagram used.
Check that this change is compatible with the wiring diagram used.
Failure to follow these instructions will result in death or serious injury.
To change the assignment of this parameter press the “ENT” key for 2 s.
I-O-
drC-
CtL-
FUN-
FLt-
COM-
2 s
2 s